Installation
3-2
Eaton BladeUPS 12 kVA Maintenance Bypass Cabinet Installation and Operation Manual P-164000130—Rev 1
www.eaton.com/powerquality
l
Control wiring is 16-22GA 75C copper wire only. Tighten to 7 lb-in, and run intercabinet wiring through
conduit.
l
After signal input wiring is connected between the MBC and the BladeUPS, the UPS firmware setting must
be set to
FORCE BYPASS
to allow the system to force a maintenance bypass mode.
NOTE
Refer to the
Eaton
®
BladeUPS
®
User’s Guide (Preassembled and Standard Systems)
For use with Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) systems
for UPS cabinet
installation, wiring information, conduit and terminal locations, and firmware
settings.
3.1.2
Unloading the Cabinet
The MBC is bolted to a wooden pallet supported by wood skids for shipping.
This procedure requires the following tools:
l
3/8-inch nut driver
l
ratchet
l
1/2-inch socket
l
6-inch extension (or longer)
l
forklift
WARNING
l
The MBC is heavy (544.31 kg/1200 lb). If unpacking instructions are not closely followed, the
cabinet may tip and cause serious injury.
l
Do not install a damaged cabinet. Report any damage to the carrier and contact your Eaton
service representative immediately.
l
Do not tilt the MBC more than 10
from vertical or the cabinet may tip over.
NOTE
Verify that the forklift is rated to handle the weight of the cabinet.
To remove the cabinet from the pallet:
1.
If not already moved, move the cabinet to the installation site, or as close as possible, before unloading
from the pallet.
l
Insert the forklift forks between the skids on the bottom of the pallet.
l
Move the pallet and cabinet close to the installation site.