Maintenance
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D July 2010
63
Step 1 - Remove cover to access I/O board
"
Input/Output cover
#
Input/Output (I/O) board
Step 2 - Replace the I/O board
1
Slide out the I/O board.
2
Label then disconnect all cables.
If an LVD is fitted it will disconnect. The load equipment will be powered by the
rectifiers. The SC200 or SC100 will show various alarms. Press any button to
silence the alarm.
3
Return the board for service. See Equipment Incident Report on page
.
4
Connect all cables to the new I/O board.
5
Check the I/O board Power On LED is on. If not see Troubleshooting on page
6
Slide in the I/O board.
7
SC200 only:
•
In
DCTools/Web
go to:
RXP
.
•
Copy the I/O board serial number from the
RXP Devices
table to the
I/O
Board to Serial Number Mapping
table to map an
IOB Number
to the I/O board
(overwrite existing serial number).
The Missing Hardware alarm will clear.
Step 3 - Replace cover