Access Power Solutions Installation Guide (APS3-400 Series)
30
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D July 2010
Step 3 - Connect at APS
1
Connect the wires to the ac terminals (see label in following diagram).
2
Tighten terminals to 10.6 - 12.4 in-lb (1.2 - 1.4Nm).
Top View
"
AC cable entry hole for up to 1"
conduit.
#
AC terminals
Step 4 - Check terminations and test insulation
1
Check all terminations are correct and are tightened.
2
Test the insulation resistance of the conductors according to local ac wiring
regulations.
3
Replace the ac terminal covers.
Procedure complete
Task 9 - Connect to the AC Supply Point
•
A suitably qualified electrician familiar with local wiring regulations must carry out the
ac connection.
Step 1 - APS systems with IEC sockets
Ignore this Step if the APS does not have IEC sockets. Go to Step 2.
1
Select the cord sets from the following table, according to the ac supply voltage.
The cord sets are available from Eaton or direct from the distributor listed.
2
Connect a cord set to each socket on the rear of the APS.