Installation
3-20
Eaton 9315/9390/9395/9395P Fixed Primary Sync Control Installation and Operation Manual
P-164000023—Rev 03
Table 3-8. Power Xpert 9395 UPS System Control Wiring Interconnections
From Secondary UPS (9395)
To Sync Control
Function
Note
TB61 TB14
Bypass Voltage
14 AWG
Twist Together
TB62
TB15
TB63
TB16
TB64
TB113
Load Voltage
14 AWG
Twist Together
TB65
TB114
TB66
TB115
TB67
–
NOT USED
–
TB68
–
NOT USED
–
TB69
TB117
Bypass Voltage Phase B Return
14 AWG
TB610
–
NOT USED
–
TB10 (AS400 Relay Card)
TB11
On Bypass Common
14 AWG
Twist Together
TB11 (AS400 Relay Card)
TB12
On Bypass NO
P31
TB122
Building Alarm 1
(Transfer to Bypass Disable)
14 AWG
Twist Together
P32
TB123
Building Alarm 1 Return
P33
TB126
Building Alarm 2
(Sync Control Trouble)
14 AWG
Twist Together
P34
TB127
Building Alarm 2 Return
From Primary UPS (9395)
To Sync Control
Function
Note
TB61 TB110
Bypass Voltage
14 AWG
Twist Together
TB62
TB111
TB63
TB112
TB64
TB17
Load Voltage
14 AWG
Twist Together
TB65
TB18
TB66
TB19
Table 3-9. Interconnections for Equipment Other Than Eaton Products (Refer to Vendor Installation Manual)
From Primary Source
To Sync Control
Description
Note
Phase A
TB110
Bypass Reference Voltage
(See Note)
Twist Together
Phase B
TB111
Phase A
TB17
Sync Voltage
Twist Together
Phase B
TB18
Phase C
TB19
NOTE:
If using the utility source as primary or a source where bypass does not exist, add jumpers to the Fixed Primary Sync Control
as shown below:
FROM
TB110
TB111
TO
TB7
TB18
Summary of Contents for 9315P
Page 1: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 8: ...This page intentionally left blank...
Page 61: ......
Page 62: ...P 164000023 2 P 164000023 3...