Installation
3-8
Eaton 9315/9390/9395/9395P Fixed Primary Sync Control Installation and Operation Manual
P-164000023—Rev 03
NOTE
If connecting multiple secondary sources to a single primary source, the Primary
Interface Enclosure must used and wired as shown in the following table. A
maximum of four secondary units can be connected to the Primary Interface
Enclosure. One Fixed Primary Sync Control should be used per secondary unit.
Table 3-5. Primary Interface Enclosure to Fixed Primary Sync Control Connections
From Primary Interface Enclosure
To FPSC #1
Wire Size
(Remarks)
Description
TB21 TB17
14 AWG
Twist Together
Primary Load Voltage
TB22
TB18
TB23
TB19
TB24
TB110
14 AWG
Twist Together
Primary Bypass Voltage
TB25
TB111
From Primary Interface Enclosure
To FPSC #2
Wire Size
(Remarks)
Description
TB31 TB17
14 AWG
Twist Together
Primary Load Voltage
TB32
TB18
TB33
TB19
TB34
TB110
14 AWG
Twist Together
Primary Bypass Voltage
TB35
TB111
From Primary Interface Enclosure
To FPSC #3
Wire Size
(Remarks)
Description
TB41 TB17
14 AWG
Twist Together
Primary Load Voltage
TB42
TB18
TB43
TB19
TB44
TB110
14 AWG
Twist Together
Primary Bypass Voltage
TB45
TB111
From Primary Interface Enclosure
To FPSC #4
Wire Size
(Remarks)
Description
TB51 TB17
14 AWG
Twist Together
Primary Load Voltage
TB52
TB18
TB53
TB19
TB54
TB110
14 AWG
Twist Together
Primary Bypass Voltage
TB55
TB111
Summary of Contents for 9315P
Page 1: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 8: ...This page intentionally left blank...
Page 61: ......
Page 62: ...P 164000023 2 P 164000023 3...