SPECIFICATIONS
Eaton 9170
+
Battery Charger Module User's Guide
S
164201399 Rev E
www.eaton.com/powerquality
14
Table 5. Model Specifications for Split-Phase Power Modules (ASY-0673)
Three-Slot Cabinet
Optional
Chargers
UPS
kVA/Watts
Input Current
(200V)
Output Current
(100/200V, 110/220V, 120/240V)
Recommended
Input Service
Heat
Dissipation
NA
3/2500
16A*
15A, 14A, 12.5A
25A
285W
(0.98 kBTU/hr)
Six-Slot Cabinet
CAUTION
Do NOT install more than three power and/or battery charger modules in a 6-slot cabinet.
Optional
Chargers
UPS
kVA/Watts
Input Current
(200V)
Output Current
(100/200V, 110/220V, 120/240V)
Recommended
Input Service
Heat
Dissipation
0
3/2500
16A
15A, 14A, 12.5A
25A
285W
(0.98 kBTU/hr)
1
3/2500
32A
15A, 14A, 12.5A
40A
570W
(1.95 kBTU/hr)
2
3/2500
48A*
15A, 14A, 12.5A
60A
860W
(2.93 kBTU/hr)
0
6/5000
32A
30A, 28A, 25A
40A
570W
(1.95 kBTU/hr)
1
6/5000
48A*
30A, 28A, 25A
60A
860W
(2.93 kBTU/hr)
0
9/7500
48A*
45A, 42A, 37.5A
60A
860W
(2.93 kBTU/hr)
Nine- and Twelve-Slot Cabinet
CAUTION
Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Optional
Chargers
UPS
kVA/Watts
Input Current
(200V)
Output Current
(100/200V, 110/220V, 120/240V)
Recommended
Input Service
Heat
Dissipation
0
3/2500
16A
15A, 14A, 12.5A
25A
285W
(0.98 kBTU/hr)
1
3/2500
32A
15A, 14A, 12.5A
40A
570W
(1.95 kBTU/hr)
2
3/2500
48A
15A, 14A, 12.5A
60A
860W
(2.93 kBTU/hr)
3
3/2500
64A
15A, 14A, 12.5A
80A
1145W
(3.90 kBTU/hr)
* Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery
cabinet ASY-0739.
Summary of Contents for 9170+ ASY-0652
Page 1: ...Powerware Series Eaton 9170 Battery Charger Module Models ASY 0652 and ASY 0675 User s Guide ...
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ... 164201399E 164201399 E ...