SPECIFICATIONS
Eaton 9170
+
Battery Charger Module User's Guide
S
164201399 Rev E
www.eaton.com/powerquality
19
Table 6. Model Specifications for Split-Phase Power Modules (ASY-0567) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION
Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Heat
Dissipation
Recommended
Input Service
Output Current
(200V, 220V, 240V)
Input Current
(200V)
UPS
kVA/Watts
Optional
Chargers
2
15/10500
102A*
75A, 70A, 62A
125A
1995W
(6.75 kBTU/hr)
0
18/12600
84A
90A, 84A, 75A
125A
1720W
(5.85 kBTU/hr)
1
18/12600
100A
90A, 84A, 75A
125A
1995W
(6.75 kBTU/hr)
* Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery
cabinet ASY-0739.