INSTALLATION
Eaton 9170
+
Battery Charger Module User's Guide
S
164201399 Rev E
www.eaton.com/powerquality
8
Battery Charger Module Installation
To install the Battery Charger Modules into the UPS or external battery
cabinet:
C
A
U
T
I
O
N
A maximum, total combination of seven (7) power modules and Battery Charger Modules are
allowed in a 12-slot cabinet.
1.
Remove the front cover(s) of the cabinet.
The covers have spring latches on the left and right sides that hold
them in place.
NOTE
Place Battery Charger Modules above the battery modules in the UPS cabinet, or in
any of the top three slots of the ASY-0739 12-slot external battery cabinet.
2.
Insert the Battery Charger Modules into the cabinet. To insert a
Battery Charger Module:
Lower the front slightly and lift the rear edge over the safety stop
on the center support rail. Keep the module handle extended until
the module is fully inserted.
Raise the Battery Charger Module handle to secure the module into
the cabinet. Be sure the handle latch snaps into place. Tighten the
thumbscrew on the handle.
3.
Reinstall the front cover(s).
4.
Turn on the UPS according to the UPS user's guide.
Summary of Contents for 9170+ ASY-0652
Page 1: ...Powerware Series Eaton 9170 Battery Charger Module Models ASY 0652 and ASY 0675 User s Guide ...
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ... 164201399E 164201399 E ...