Chapter 5
Troubleshooting
Alarm Messages
When the Battery Charger Module is located in a UPS cabinet, the UPS
displays alarm messages which involve the Battery Charger Module.
Refer to “Troubleshooting” in the UPS user's guide.
Audible Alarms and UPS Conditions
When the Battery Charger Module is located in an external battery
cabinet, the Battery Charger Module uses an audible alarm feature to
alert you of potential power problems. When the alarm is activated, the
Battery Charger Module beeps in different intervals according to a
particular condition. Use Table 7 to determine and resolve the alarms
and conditions.
Table 7. Battery Charger Module Audible Alarms
Audible Alarm
Condition
Action
1 short (0.5 sec)
Startup
Nothing. Module is operating normally.
1 short, pause, 2 short
Shorted output error
Call your service representative.
1 short, pause, 3 short
Battery overvoltage error
Call your service representative.
1 short, pause, 4 short
Charger failure
Call your service representative.