background image

7

Instruction Booklet 

IL70C1080H03

Effective May 2014

Instructions for Field Installing Ground Fault Alarm/Power
Supply Modules into Digitrip 520M Equipped Eaton
Magnum and Magnum DS Circuit Breakers

EATON www.eaton.com

10.0  Post Installation Testing

10.1 When to Test

Testing prior to start-up can best be accomplished with the breaker 

out of its cell or in the Test, Disconnected, or Withdrawn (or 

Removed) cell positions.

 

CAUTION

TESTING A CIRCUIT BREAKER WHILE IT IS IN SERVICE AND CARRYING 

LOAD CURRENT IS NOT RECOMMENDED.   

 

TESTING OF A CIRCUIT BREAKER THAT RESULTS IN THE TRIPPING OF THE 

CIRCUIT BREAKER SHOULD BE DONE ONLY WITH THE CIRCUIT BREAKER 

IN THE TEST OR DISCONNECTED CELL POSITIONS OR WHILE THE CIRCUIT 

BREAKER IS ON A TEST BENCH.

 

CAUTION

ANY TRIPPING OPERATION WILL CAUSE DISRUPTION OF SERVICE 

AND POSSIBLE PERSONAL INJURY, RESULTING IN THE UNNECESSARY 

SWITCHING OF CONNECTED EQUIPMENT.

10.2 Code Requirements

The NEC, under Article 230-95-C, requires that any ground fault pro-

tection system be performance tested when first installed.  Conduct 

tests in accordance with the approved instructions provided with the 

equipment.  Make a written record of this test and make the results 

available to the authority having inspection jurisdiction.

10.3 Standard Requirements

As a follow-up to the basic performance requirements stipulated 

by the NEC, UL Standard No. 1053 requires that certain minimum 

instructions must accompany each ground fault protection system.  

These statements (Section 5.4.3), detailed testing information, plus 

a copy of the record forms can be found in the Instructional Leaflet 

which came with your breaker.  (I.L.  70C1037) 

10.4 Test Methods - (Refer to Figure 2)

10.4.1 Power Up Check

Upon energizing the trip unit with the correct auxiliary power control 

voltage onto secondary contacts A-14 and A-15, confirm that the sta-

tus LED and LCD display are functioning.
If the Digitrip does not have a ground element and the module was 

installed just for the powering of the LED display, then perform an 

overload test at 200% to verify tripping (secondary injection test 

with a test kit).  This would complete the verification sequence.  If a 

ground element is involved, continue with the following tests.

10.4.2  Secondary Injection Test

An AC current of 1 Amp input can be injected onto the breaker 

secondary contacts B-4 and B-5.  This will trigger the Ground Alarm 

indicator to function and close contacts A-10 and A-11.

10.4.3  Primary Injection Test

A primary current higher than the Ground Current Pickup setting, 

when applied to a pole of the circuit breaker, will trigger the Ground 

Alarm indicator to function.

10.4.4  General Test Instructions For Secondary and Primary 

I

njection Methods

The interconnected system must be evaluated only by qualified per-

sonnel and in accordance with the equipment assembler’s detailed 

instructions.  
To avoid improper operations following apparently correct simulated 

test operations, the polarity of the neutral sensor connections (if 

used) must agree with the equipment assembler’s detailed instruc-

tions.  Where a question exists, consult the specifying engineer and/

or equipment assembler.

 

WARNING

DO NOT ATTEMPT TO INSTALL, TEST, OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. 

 

DE-ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER 

BEFORE PERFORMING MAINTENANCE OR TESTS.

 

WARNING

PERSONAL INJURY CAN OCCUR WHEN WORKING ON POWER SYSTEMS.  

ALWAYS TURN OFF POWER SUPPLYING BREAKER BEFORE CONDUCTING 

TESTS.  TEST OUT OF THE CELL, IF POSSIBLE.  THERE IS A HAZARD OF 

ELECTRICAL SHOCK OR BURN WHENEVER WORKING IN OR AROUND 

ELECTRICAL EQUIPMENT.

Verify the grounding points of the system using high voltage testers 

and resistance bridges to ensure that ground paths do not exist that 

could bypass the sensors.  
Use a low-voltage (0 to 24 volt), high-current, AC source to apply a 

test current of 125% of the Digitrip unit ground fault pickup setting 

through one phase of the circuit breaker.  This should cause the 

breaker to trip (on LSIG style trip units) in less than 1 second and 

operate the alarm indicator.  Reset the breaker and the alarm indica-

tor.  Repeat the test on the other two phases (see Figure 10).

Figure 10.  Connection Details for Conducting Single Pole, 

Single Phase Current Tests with the Breaker Removed from the 

Cell.

Apply the same current as described above through one phase of 

the breaker, returning through the neutral sensor if so equipped.  The 

breaker should not trip and the alarm indicator should not operate.  

Repeat the test on the other two phases.

Summary of Contents for 70C1081G01

Page 1: ...tion Preparation 3 6 0 Installation Procedure 3 7 0 Mounting the Module 5 8 0 Wiring Harnesses 5 9 0 Reassembly 6 10 0 Post Installation Testing 7 11 0 Standards 8 Effective May 2014 Supercedes April...

Page 2: ...02C83G01 Shown Figure 2 Wiring Diagram for 520M Models and Ground Alarm Power Supply Modules 1 1 Auxiliary Power Ground Alarm When the module is wired as shown in Figure 2 it will provide an auxiliary...

Page 3: ...reparation 5 1 Remove Breaker from Line Ascertain that the breaker is completely powered down during the Ground Alarm Power Supply module installation If you are unsure as to whether or not the unit i...

Page 4: ...hor the steel trip deck plate into the mounting boss Be careful not to damage the Trip Indicator Assembly and Over Current Trip Switch Bell Alarm if your breaker contains this option Note N Observe ho...

Page 5: ...T THAT THE TIE WRAPS ARE TRIMMED AND THAT THE NEW HARNESSES AND EXISTING WIRING BE TUCKED NEATLY BACK INTO THE BREAKER FRAME LOOSE OR STRAY WIRES MIGHT INTERFERE WITH PROPER FIT AND ALIGNMENT OF THE T...

Page 6: ...th the sockets in the cavity The plug should fit with a slight insertion force Now or If the rating plug was left inside the trip unit use a 0 125 3 2 mm wide screwdriver to tighten the M4 screw until...

Page 7: ...following tests 10 4 2 Secondary Injection Test An AC current of 1 Amp input can be injected onto the breaker secondary contacts B 4 and B 5 This will trigger the Ground Alarm indicator to function a...

Page 8: ...test kit to initiate a ground trip and verify the alarm contact closure and breaker trip action The test port is located on the front left hand corner of the Trip Unit To access the port remove the pl...

Page 9: ...Booklet IL70C1080H03 Effective May 2014 Instructions for Field Installing Ground Fault Alarm Power Supply Modules into Digitrip 520M Equipped Eaton Magnum and Magnum DS Circuit Breakers EATON www eat...

Page 10: ...purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is...

Reviews: