Instruction Booklet 

IL70C1080H03

Effective May 2014

Instructions for Field Installing Ground Fault Alarm/Power

Supply Modules into Digitrip 520M Equipped Eaton

Magnum and Magnum DS Circuit Breakers

EATON www.eaton.com

otee:

N

The recommendations and information contained herein are based on 

experience and judgement, but should not be considered to be all inclusive 

or to cover every application or circumstance which may arise.  If you have 

any questions or need further information or instructions, please contact your 

local representative or the Customer Support Center at 1-800-356-1234.

1.0  General Description (of the Ground 
Alarm / Power Supply Module)

The Ground Alarm / Power Supply Module (see Figure 1) is an 

optional accessory for the Digitrip 520M trip unit.  It mounts under-

neath the metal trip unit mounting plate in the Magnum breaker.  

When wired (see Figure 2), it will provide an auxiliary power supply 

for the Digitrip 520M’s LCD meter display, when the circuit breaker 

is lightly loaded.  (On non-ground fault style trip units, this will be its 

ONLY function.) 
A second function of the module is to provide Ground Trip or Ground 

Alarm Only contact closure via the relay supplied in the module.  

This is assuming the Digitrip 520M is already equipped with ground 

trip or ground alarm functionality.  The following input voltage ratings 

of the module it self are covered: 120 Vac, 230 Vac and 24/48 Vdc.

Figure 1. Ground Alarm / Power Supply Modules  

Style #7802C83G01 Shown.

Figure 2. Wiring Diagram for 520M Models and Ground Alarm / 

Power Supply Modules.

1.1  Auxiliary Power & Ground Alarm

When the module is wired (as shown in Figure 2), it will provide an 

auxiliary power supply so that the 520M/520M

i

 liquid crystal dis-

play (LCD) will be functional even when the circuit breaker has no 

load.  A Digitrip 520M unit 

without

 auxiliary power will not display 

data until load current reaches approximately 25% 1 phase or 10%3 

phase of the (

I

 n) rating.  

A second function of the module is to provide either aground trip or 

ground alarm only output contact via the relay supplied in the mod-

ule.  On Digitrip 520M models with ground fault protection, an LED 

on the front of the unit also provides an indication of ground fault 

trip.

1.2 Ground Fault Trip 

When the Ground Alarm/Power Supply module is used with the 

5MLSIG model, this unit will provide ground fault trip contacts when 

the circuit breaker trips on a ground fault.  You must then push the 

Reset button on the Digitrip in order to reset the contacts (see 

Figure 2, Note 3).

1.3  Ground Fault Alarm

A ground fault alarm alerts a User to a ground fault condition with-

out tripping the circuit breaker.  (This is applicable when using the 

5MLSIA model.)  A red Alarm Only LED on the front of the trip unit 

will indicate the presence of a ground fault condition that exceeds 

the programmed setting.
The ground fault alarm relay is energized when the ground current 

continuously exceeds the ground fault pickup setting for a time in 

excess of a 0.1 second delay.  The alarm relay will reset automati-

cally if the ground current is less than the ground fault pickup (see 

Figure 2, Note 4).

Summary of Contents for 70C1081G01

Page 1: ...tion Preparation 3 6 0 Installation Procedure 3 7 0 Mounting the Module 5 8 0 Wiring Harnesses 5 9 0 Reassembly 6 10 0 Post Installation Testing 7 11 0 Standards 8 Effective May 2014 Supercedes April...

Page 2: ...02C83G01 Shown Figure 2 Wiring Diagram for 520M Models and Ground Alarm Power Supply Modules 1 1 Auxiliary Power Ground Alarm When the module is wired as shown in Figure 2 it will provide an auxiliary...

Page 3: ...reparation 5 1 Remove Breaker from Line Ascertain that the breaker is completely powered down during the Ground Alarm Power Supply module installation If you are unsure as to whether or not the unit i...

Page 4: ...hor the steel trip deck plate into the mounting boss Be careful not to damage the Trip Indicator Assembly and Over Current Trip Switch Bell Alarm if your breaker contains this option Note N Observe ho...

Page 5: ...T THAT THE TIE WRAPS ARE TRIMMED AND THAT THE NEW HARNESSES AND EXISTING WIRING BE TUCKED NEATLY BACK INTO THE BREAKER FRAME LOOSE OR STRAY WIRES MIGHT INTERFERE WITH PROPER FIT AND ALIGNMENT OF THE T...

Page 6: ...th the sockets in the cavity The plug should fit with a slight insertion force Now or If the rating plug was left inside the trip unit use a 0 125 3 2 mm wide screwdriver to tighten the M4 screw until...

Page 7: ...following tests 10 4 2 Secondary Injection Test An AC current of 1 Amp input can be injected onto the breaker secondary contacts B 4 and B 5 This will trigger the Ground Alarm indicator to function a...

Page 8: ...test kit to initiate a ground trip and verify the alarm contact closure and breaker trip action The test port is located on the front left hand corner of the Trip Unit To access the port remove the pl...

Page 9: ...Booklet IL70C1080H03 Effective May 2014 Instructions for Field Installing Ground Fault Alarm Power Supply Modules into Digitrip 520M Equipped Eaton Magnum and Magnum DS Circuit Breakers EATON www eat...

Page 10: ...purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is...

Reviews: