background image

5

Instruction Booklet 

IL70C1080H03

Effective May 2014

Instructions for Field Installing Ground Fault Alarm/Power
Supply Modules into Digitrip 520M Equipped Eaton
Magnum and Magnum DS Circuit Breakers

EATON www.eaton.com

7.0  Mounting the Module

Carefully remove any wire ties and move existing wiring to the left.  

The module mounts directly under the steel plate so that the hole in 

the module aligns with the 4 mm threaded insert.  Hold the module 

against the mounting surface to confirm correct positioning.  Take 

one of the supplied self tapping screws and partially screw it into the 

bottom retaining boss for the module.  The screw anchoring tabs for 

the module are slotted.
Slide the bottom tab of the module behind the partially inserted 

screw.  Take the second screw and place it in the other slotted notch 

on the top of the module and anchor the unit in place in the breaker.  

Now go back and tighten the bottom retaining screw and ascertain 

that the Ground Alarm / Power Supply Module is firmly seated in the 

Magnum frame.

8.0  Wiring Harnesses

Two wiring harnesses must be attached to the Ground Alarm / Power 

Supply Module.  The first, a three conductor connector, is already 

pre-wired into the breaker at the factory.  The second is supplied 

with the field installable upgrade kit.  It comes ready to install with 

a four conductor connector on one side and male pins on the other 

which are inserted into the Secondary Block “A” which is a black con-

nector on the top left side of the breaker

8.1 Preparing the Harness

Using several of the supplied tie wraps, secure the four conductor 

harness into a common bundle.  Cleanly trim the excess tails from 

the tie wraps.

 

CAUTION

IT IS IMPORTANT THAT THE TIE WRAPS ARE TRIMMED AND THAT THE 

NEW HARNESSES AND EXISTING WIRING BE TUCKED NEATLY BACK INTO 

THE BREAKER FRAME.  LOOSE OR STRAY WIRES MIGHT INTERFERE WITH 

PROPER FIT AND ALIGNMENT OF THE TRIP UNIT.  ADDITIONALLY, THIS 

SAME SITUATION MIGHT INHIBIT MOVEMENT OR OPERATION OF CERTAIN 

MECHANICAL COMPONENTS WITHIN THE BREAKER.

8.2 Attaching Harnesses to the Module

Take the pre-wired, three conductor connector with the locking edge 

facing up and push firmly into place on the three conductor pin set 

(J3) on the left side of the top of the module.  Confirm that the con-

nector is locked in place.
Next, take the four conductor connector and similarly attach it to the 

four conductor pin set (J4) on the right side of the top of the mod-

ule.  Confirm that it is secure.

8.3 Running the Harness

Rout the end of the four conductor harness with the four pins from 

the Ground Alarm Power Supply Module between the bosses up 

to the Secondary Block “A.”  Be sure that the wires do not interfere 

with any moving parts.

8.4 Wiring the Secondary Block “A”

The ends of the four conductor harness are to be connected to the 

Secondary Block “A” on the top, left side of the breaker (see Figure 

7).  The wires are marked A-10, A-11, A-14, and A15.  According to 

the label on the block, insert them into the proper terminal slots.  

This is done simply by pushing them in until they lock.  After the 

audible “click,” confirm that they are secure by slightly pulling on 

each wire.
Tuck away and tie wrap all wiring neatly so that it will not interfere 

with any mechanical operation or prevent improper fit of reassem-

bled components.

Figure 7.  Wiring Secondary Block “A”.

otee:

N

The AMP

 extraction tool is not actually required for the installation of 

the Ground Alarm / Power Supply Module.  It is needed only if the pins are 

accidently inserted into the wrong locations in Secondary Block “A” and have 

to be removed and reinserted.

Trip Indicator Assembly 

(Over Current Trip Switch / Bell Alram)

Summary of Contents for 70C1081G01

Page 1: ...tion Preparation 3 6 0 Installation Procedure 3 7 0 Mounting the Module 5 8 0 Wiring Harnesses 5 9 0 Reassembly 6 10 0 Post Installation Testing 7 11 0 Standards 8 Effective May 2014 Supercedes April...

Page 2: ...02C83G01 Shown Figure 2 Wiring Diagram for 520M Models and Ground Alarm Power Supply Modules 1 1 Auxiliary Power Ground Alarm When the module is wired as shown in Figure 2 it will provide an auxiliary...

Page 3: ...reparation 5 1 Remove Breaker from Line Ascertain that the breaker is completely powered down during the Ground Alarm Power Supply module installation If you are unsure as to whether or not the unit i...

Page 4: ...hor the steel trip deck plate into the mounting boss Be careful not to damage the Trip Indicator Assembly and Over Current Trip Switch Bell Alarm if your breaker contains this option Note N Observe ho...

Page 5: ...T THAT THE TIE WRAPS ARE TRIMMED AND THAT THE NEW HARNESSES AND EXISTING WIRING BE TUCKED NEATLY BACK INTO THE BREAKER FRAME LOOSE OR STRAY WIRES MIGHT INTERFERE WITH PROPER FIT AND ALIGNMENT OF THE T...

Page 6: ...th the sockets in the cavity The plug should fit with a slight insertion force Now or If the rating plug was left inside the trip unit use a 0 125 3 2 mm wide screwdriver to tighten the M4 screw until...

Page 7: ...following tests 10 4 2 Secondary Injection Test An AC current of 1 Amp input can be injected onto the breaker secondary contacts B 4 and B 5 This will trigger the Ground Alarm indicator to function a...

Page 8: ...test kit to initiate a ground trip and verify the alarm contact closure and breaker trip action The test port is located on the front left hand corner of the Trip Unit To access the port remove the pl...

Page 9: ...Booklet IL70C1080H03 Effective May 2014 Instructions for Field Installing Ground Fault Alarm Power Supply Modules into Digitrip 520M Equipped Eaton Magnum and Magnum DS Circuit Breakers EATON www eat...

Page 10: ...purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is...

Reviews: