background image

6

Instruction Booklet 

IL70C1080H03

Effective May 2014

Instructions for Field Installing Ground Fault Alarm/Power

Supply Modules into Digitrip 520M Equipped Eaton

Magnum and Magnum DS Circuit Breakers

EATON www.eaton.com

9.0  Reassembly

9.1 Replacing the Trip Deck (Mounting Plate)

Swing the steel trip unit mounting plate down onto the two lower 

partially loosened attachment screws.  Tuck all wiring bundles 

neatly behind it so as not to capture wires between the module 

and the steel deck.  Position the mounting tabs of the Trip Indicator 

Assembly (also the Overcurrent Trip Switch / Bell Alarm if this option 

is attached) behind the steel Trip Unit Mounting Plate (see Figure 8).

Figure 8. Proper Seating of Trip Indicator Assembly Behind the 

Steel Trip Unit Mounting Deck.

Confirm that the steel wireform for the Trip Indicator Assembly is not 

bound nor its operation interfered with (see Figure 9).  Replace the 

two top screws that hold the steel Trip Unit Mounting Plate in place.  

Tighten all four appropriately and confirm that the trip deck plate is 

firmly seated.

Figure 9. The Steel Wireform of the Trip Indicator Assembly.

9.2  Reinstalling the Trip Unit

Align the Digitrip unit with the two guide pins on the plate and 

spring clip of the Magnum Circuit Breaker (see previous Figure 5).  

Press the unit into the breaker until the pins engage into the connec-

tors and the lower spring clip engages over the Digitrip’s housing.

 

WARNING

DO NOT ENERGIZE THE MAGNUM BREAKER WITH THE DIGITRIP REMOVED 

OR DISCONNECTED FROM ITS CONNECTOR.  DAMAGE TO INTERNAL 

CURRENT TRANSFORMERS MAY OCCUR DUE TO AN OPEN CIRCUIT 

CONDITION.

9.3 Reinserting and Securing the Rating Plug

If the rating plug was removed from the trip unit, carefully, insert 

it back into the cavity on the right-hand side of the trip unit.  Align 

the three pins on the plug with the sockets in the cavity.  The plug 

should fit with a slight insertion force.
Now (or If the rating plug was left inside the trip unit), use a 0.125” 

(3.2 mm) wide screwdriver to tighten the M4 screw until the screw 

head contacts the rating plug with 1 in.-lb (1.36 N·m) of torque.  

This will secure the plug and the trip unit into the circuit breaker (as 

removed in previous Figure 4).
Close the rating plug door.

 

CAUTION

DO NOT FORCE THE RATING PLUG INTO THE CAVITY.  FURTHERMORE, THE 

M4 SCREW SHOULD BE TIGHTENED ONLY UNTIL IT IS SNUG.  DO NOT USE 

A LARGE SCREWDRIVER.  A 1/8” (3 MM) WIDE SCREWDRIVER BLADE IS 

ADEQUATE.

 

CAUTION

BE SURE TO CHECK THAT THE SENSOR RATING MATCHES THAT PRINTED 

ON THE RATING PLUG DOOR.  INSTALLING A RATING PLUG THAT 

DOES NOT MATCH THE SENSOR RATING CAN PRODUCE SERIOUS MIS-

COORDINATION AND/OR FAILURE OF THE PROTECTION SYSTEM. 

 

IF A RATING PLUG IS NOT INSTALLED IN THE TRIP UNIT, THE UNIT WILL 

INITIATE A TRIP WHEN IT IS ENERGIZED BY CONTROL POWER OR BY LINE 

CURRENT.

9.4 Final Internal Visual Inspection

Before proceeding any further, do a visual inspection to insure that 

none of the breaker’s internal wiring might hamper any mechanical 

operation or compromise proper fit of any component.  Use any 

remaining tie wraps to secure any wires which might be loose.

9.5 Replacing the Front Cover

Partially pull down the charging handle on the front of the breaker.  

Slide the breaker cover over the handle and into place on the breaker 

frame.  Using the 10mm ratchet or driver, tighten all four retaining 

bolts in each corner of the cover to 25 to 35 in.-lb (33.90 - 47.45 

N·m) of torque.  Latch the breaker and reset the red flag on the Trip 

Indicator Assembly which protrudes from the front cover above the 

Trip Unit.  Proceed with the test sequence.

otee:

N

At this time, it is highly recommended that the proper accessory label 

be placed in the “Accessories” area of the front cover.  Chose the sticker 

that matches the Trip Unit Power voltage of the style installed:

24-48 Vdc (#70C1081G01), 120 Vac (#70C1081G02) or  

240 Vac (#70C1081G03).

Summary of Contents for 70C1081G01

Page 1: ...tion Preparation 3 6 0 Installation Procedure 3 7 0 Mounting the Module 5 8 0 Wiring Harnesses 5 9 0 Reassembly 6 10 0 Post Installation Testing 7 11 0 Standards 8 Effective May 2014 Supercedes April...

Page 2: ...02C83G01 Shown Figure 2 Wiring Diagram for 520M Models and Ground Alarm Power Supply Modules 1 1 Auxiliary Power Ground Alarm When the module is wired as shown in Figure 2 it will provide an auxiliary...

Page 3: ...reparation 5 1 Remove Breaker from Line Ascertain that the breaker is completely powered down during the Ground Alarm Power Supply module installation If you are unsure as to whether or not the unit i...

Page 4: ...hor the steel trip deck plate into the mounting boss Be careful not to damage the Trip Indicator Assembly and Over Current Trip Switch Bell Alarm if your breaker contains this option Note N Observe ho...

Page 5: ...T THAT THE TIE WRAPS ARE TRIMMED AND THAT THE NEW HARNESSES AND EXISTING WIRING BE TUCKED NEATLY BACK INTO THE BREAKER FRAME LOOSE OR STRAY WIRES MIGHT INTERFERE WITH PROPER FIT AND ALIGNMENT OF THE T...

Page 6: ...th the sockets in the cavity The plug should fit with a slight insertion force Now or If the rating plug was left inside the trip unit use a 0 125 3 2 mm wide screwdriver to tighten the M4 screw until...

Page 7: ...following tests 10 4 2 Secondary Injection Test An AC current of 1 Amp input can be injected onto the breaker secondary contacts B 4 and B 5 This will trigger the Ground Alarm indicator to function a...

Page 8: ...test kit to initiate a ground trip and verify the alarm contact closure and breaker trip action The test port is located on the front left hand corner of the Trip Unit To access the port remove the pl...

Page 9: ...Booklet IL70C1080H03 Effective May 2014 Instructions for Field Installing Ground Fault Alarm Power Supply Modules into Digitrip 520M Equipped Eaton Magnum and Magnum DS Circuit Breakers EATON www eat...

Page 10: ...purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is...

Reviews: