EasyIO EIO-75 Series Manual Download Page 5

EasyIO

EIO-75 032719

Measurement Displays

The room interfaces can show up to 3 temperatures (sensor 1, sensor 2, sensor 3) in the ACTION 
CIRCLE. With the RH humidity sensor option, the relative humidity sensor is also displayed in the 
ACTION CIRCLE. 

Outside

50

.1

°F

Sensor 1 can display the external sensor RI1 temperature, or temperature can be 
set over the network (if 

Sensor1 Source 

has been set to network). The description 

for the temperature can be changed via 

Sensor1 Text

 parameter in the 

configuration pages. By setting the description to 

Disabled

, the sensor reading is 

not displayed on the screen. 

Floor

70

.1

°F

Sensor 2 can display the external sensor RI2 temperature, or temperature can be 
set over the network (if 

Sensor2 Source 

has been set to network). The description 

for the temperature can be changed via 

Sensor2 Text

 parameter in the 

configuration pages. By setting the description to 

Disabled

, the sensor reading is 

not displayed on the screen. 

Room

20

.1

°C

Sensor 3 can display the built-in sensor temperature, or temperature can be set 
over the network (if 

Sensor3 Source 

has been set to network). The description for 

the temperature can be changed via 

Sensor3 Text

 parameter in the configuration 

pages. By setting the description to 

Disabled

, the sensor reading is not displayed 

on the screen. 

Target Units

Note: If all sensor displays are 

Disabled,

 the ACTION CIRCLE displays the last drawn image.

Inside the large circle on the HOME SCREEN the 

EIO

-75 shows the target value. As default the 

units are in temperature (Fahrenheit / Celcius). It is possible to change the units to ’percentage’ to 
display the target values for percentage based control.

Centigrade to Fahrenheit 
Display

The 

EIO-

75 Series have Fahrenheit to 

Celcius icons on the top of the Home Screen. 
From this icon it is possible to change the 
units by touching this icon.

Target

65

.0

°F

Room

72

.8

°F

°F

°C

UNIT SELECTION

Target

18

.3

°C

Room

22

.7

°C

°F

°C

This option is particularly useful in hospitality 
applications where the client base is 
expected to be international.

NOTE: 

EIO

-75 series has all configuration 

parameters displayed in Fahrenheit only.

Further Settings and 
Information

The FURTHER SETTINGS shows additional user settings options on the 

EIO

 room interfaces:-

OFF icon to switch device to OFF (OFF icon is displayed here only if OFF icon has been enabled 
and the PARTY (BOOST) button has also been enabled)

LOCK icon is used to lock the device. Number of different lock modes options exist.

CLEANING icon is used to enable timed cleaning mode.

COG WHEEL icon allows entry to the maintenance mode.

EasyIO Holdings
www.easyio.com

Summary of Contents for EIO-75 Series

Page 1: ...rides Measurement EIO 75 Model Type EIO 75 BAC BACnet MSTP Touchscreen LCD Room Interface 24Vac dc Power Supply 24V rated relay degF default EIO 75 BAC CO2 BACnet MSTP Touchscreen LCD Room Interface C...

Page 2: ...ssing 0 to 127 via Touchscreen Device ID Default 651000 MAC Address User Configured Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits Connections Terminal Connections Re...

Page 3: ...YOUT 24VAC 30VDC 5A Relay Contact RELAYCOM 24VAC 30VDC 5A Relay Contact 24V 24Vac dc Supply 0V 0V Supply Rin1 Remote NTC10 Temperature Sensor Input 1 Rin2 Remote NTC10 Temperature Sensor Input 2 Din V...

Page 4: ...BLUE DISPLAY SRI 75 WITH FAN SPEED DEG C 21 5 C Room 20 1 C A CONTROL MODE AUTO HEATING COOLING FAN VENTILATION FAN F C F C F C The EIO 75 room interface home screen has four touch sensitive areas tha...

Page 5: ...ration pages By setting the description to Disabled the sensor reading is not displayed on the screen Target Units Note If all sensor displays are Disabled the ACTION CIRCLE displays the last drawn im...

Page 6: ...5 has fan icon and line bar to indicate the fan speed It is also possible to use the line bar only to indicate other signals by disabling the fan icon The fan and line bar display is configured by a p...

Page 7: ...ents M and Auto A When auto is selected the display returns to show the speed set over the network 3 STEP AUTO fan speed rotates between OFF M 2 segments M 4 segments M 6 seg ments M and Auto A When a...

Page 8: ...mode OFF Mode Icon OFF MODE CANCEL ICON Room 73 1 F 46 0 F OFF MODE ICON TO ACTIVATE OFF MODE Room 73 1 F 71 5 F OFF MODE ACTIVE OFF MODE INACTIVE TARGET VALUE DIMMED WHEN OFF MODE ACTIVE F C F C The...

Page 9: ...frosting 71 5 F Room 20 1 F Target A FROST ICON F C Cleaning Mode After entering FURTHER INFORMATION screen by selecting the CLEANING icon it is possible to activate the cleaning mode The EIO 75 will...

Page 10: ...the Programmed Times NO INPUT All Buttons Locked Alarm Display When entering FURTHER INFORMATION AND SETTINGS screen and an alarm is active select the alarm icon for more information FURTHER SETTINGS...

Page 11: ...e humidity sensor for room space humidity measurement The humidity reading is displayed inside the SMALL ACTION CIRCLE display as default enabled option to disable through configuration pages and avai...

Page 12: ...n Range Sensor 1 Source Sensor 1 Source When set to Hardware reads RI1 status monitoring over the network is always active 0 Hardware RI1 1 Network Default Sensor 2 Source Sensor 2 Source When set to...

Page 13: ...light Brightness 0 20 default 5 Enable Lights Icon Enable Lights Icon Network Variable 0 Disabled default 1 Enabled Enable AC Icon Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable L...

Page 14: ...sabled removes Sensor1 Text and Measurement from Display Sensor 3 Text Description for the Sensor3 Built In Sensor Network Default 1 Room Note Disabled removes Sensor1 Text and Measurement from Displa...

Page 15: ...101 Relay Output Status 0 1 Off On 102 Time Clock Status not available 0 1 Off On 103 Light Switch Status 0 1 Off On 104 A C Switch Status 0 1 Off On 105 OFF Mode Status 0 1 Off On 106 Screen Lock Sta...

Page 16: ...8 0 122 0 C F Default 0 0 109 Fan Manual Control Mode Unsigned 16 0 4 0 Disabled default 1 1 Step 2 2 Step 3 3 Step 4 6 Step 5 1 Step Auto 6 2 Step Auto 7 3 Step Auto 8 6 Step Auto 9 Advanced 110 Fan...

Page 17: ...None default 1 Override On 2 Override Off 132 Override Lock Mode Note The parameter returns automatically to 0 allowing local control Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode 1...

Page 18: ...end Switching Time 1 Unsigned 16 0 2400 0 2400 Default 0600 211 Tuesday Weekend Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 212 Tuesday Weekend Switching Time 3 Unsigned 16 0 2400 0 2400 D...

Page 19: ...t 1700 255 Saturday Switching Time 1 Target Unsigned 16 0 1 0 1 Default 0 256 Saturday Switching Time 2 Target Unsigned 16 0 1 0 1 Default 0 257 Saturday Switching Time 3 Target Unsigned 16 0 1 0 1 De...

Page 20: ...or 1 RI1 AI 4 Sensor 2 RI2 Analogue Value 5 AV 0 Nominal Setpoint AV 1 Sensor 1 Temp AV 2 Sensor 2 Temp AV 3 Sensor 3 Temp AV 4 Brightness Binary Input 4 BI 0 Digital Input DI1 BI 1 Boost Party Mode S...

Page 21: ...Name ID Attributes Range Default Object Identifier R W 20 Object Name R W 32 Characters Max Concatenation of product type and MAC address i e SRI001 Object Type R Device System Status R STATUS_OPERAT...

Page 22: ...1 On Off Boost workable only 2 Temp settings only available 3 All buttons disabled 40118 Show Unit Swap Icon Unsigned 0 Disabled 1 Enabled default 40119 Built In Sensor Calibration REAL 10 0 10 0 C F...

Page 23: ...Default 0 Disabled Note Disabled removes the text and measurement from the display Unsigned 40141 Sensor 3 Text Built in Network Sensor Default 1 Room Note Disabled removes the text and measurement fr...