EasyIO
EIO-75 032719
EasyIO Holdings
www.easyio.com
FUNCTION CODE 03 - READ HOLDING REGISTERS (For Modicon Addressing Add 40,000)
FUNCTION CODE 06 - WRITE SINGLE HOLDING REGISTER
FUNCTION CODE 16 - WRITE MULTIPLE HOLDING REGISTERS
100
Nominal Setpoint
Unsigned 16
0...990
0...99.9 (Default 70.0)
(°C/°F/%)
101
Setpoint Unit
Unsigned 16
0..1
0 = Temperature (Default)
1 = Percentage
102
Sensor 3 Source
Unsigned 16
0..1
0 = Buillt-In Sensor (Default)
1 = Network Sensor
103
Sensor 3 Network Temperature
Signed 16
-580...1220
-58.0...122.0°C/°F (Default 0.0)
104
Minimum Setpoint
Unsigned 16
0...990
0.0...99.9°C/°F/% (Default 57°F)
105
Maximum Setpoint
Unsigned 16
0...990
0.0...99.9°C/°F/% (Default 86°F)
106
color
Ring Mode
Unsigned 16
0..10
0 = White
1 = Red
2 = Blue
3 = Green
4 = Orange
5 = Yellow
6 = Magenta
7 = Cyan
8 = Sensor 1
9 = Sensor 2
10 = Sensor 3 (Default)
107
Sensor 1 Source
Unsigned 16
0..1
0 = RI1
1 = Network Sensor (Default)
108
Sensor 1 Network Temperature
Signed 16
-580...1220
-58.0...122.0°C/°F (Default 0.0)
109
Fan Manual Control Mode
Unsigned 16
0..4
0 = Disabled (default)
1 = 1-Step
2 = 2-Step
3 = 3-Step
4 = 6-Step
5 = 1-Step + Auto
6 = 2-Step + Auto
7 = 3-Step + Auto
8 = 6-Step + Auto
9 = Advanced
110
Fan Display
Unsigned 16
0..5
0 = Disabled (default)
1 = Bar & Fan
2 = Bar
3 = Fan
4 = Coloured Bar & Fan
5 = Coloured Bar
111
Fan Speed Override
Unsigned 16
0..6
0..6
112
Enable Mode Icon
Unsigned 16
0..6
0 = Disabled (default)
1 = Htg/Clg
2 = Htg/Clg/Fan
3 = Auto/Htg/Clg
4 = Auto/Hhg/Clg/Fan
5 = Auto/Htg/Fan
6 = Auto/Clg/Fan
113
Digital Input Mode
Unsigned 16
0..6
0 = Disabled (no
EIO
effect)
1 = Close for ECO
2 = Open for ECO
3 = Close for OFF
4 = Open for OFF
5 = DI Contact Alarm
6 = Network
114
Digital Input Delay
Unsigned 16
0..7200
0..7200 seconds (Default 0s)
115
Enable Lights Symbol
Unsigned 16
0..1
0 = Disabled (default)
1 = Enabled
116
Enable AC Symbol
Unsigned 16
0..1
0 = Disabled (default)
1 = Enabled
117
Lock Mode
Unsigned 16
0..3
0 = Lock mode disabled (default)
1 = On/Off/Boost workable only
2 = Temp settings only available
3 = All buttons disabled
118
Show Unit Swap
Unsigned 16
0..1
0 = Disabled
1 = Enabled (default)
Register
Parameter Description
Data Type
Raw Data
Range