Fault information
Possible cause
Action
instance output of
inverter after sudden
change or short current
on grid
specifications. After failure recovery, the
inverter automatically recovers to normal
operation.
2. If the alarm is repeated, please contact the
distributor or after-sales service center.
OUT RMS Over
CURR
OUT Over FREQ
OUT Low FREQ
INV FAST Over
CURR
Protection resulting
from abnormal
instance
output of inverter after
sudden change or
short current on grid
1. Check whether the external load and the grid
exceed the range specified in the inverter
specifications. After failure recovery, the
inverter automatically recovers to normal
operation.
2. If the alarm is repeated, please contact the
distributor or after-sales service center.
INV RMS Over VOLT
INV RMS Low VOLT
INV Inductor CURR
Limit
The output voltage of
the inverter is out of the
range of protection
value.
1. Check whether the external load exceeds
the
range
specified
in
the
inverter
specifications. After failure recovery, the
inverter automatically returns to the normal
operation status.
2. If the alarm is repeated, please contact the
distributor or after-sales service center.
INV Inductor Over
CURR
INV VOLT DC
Component Over
The DC current
component of the grid
current exceeds the
allowable range.
1. Wait until the inverter recovers.
2. Check the grid voltage or frequency. If the
grid voltage or frequency exceeds the
allowable range of the inverter protection
parameters, report the grid company.
3. If the grid voltage or frequency is within the
allowable range, please contact the distributor
or after-sales service center.
INV CURR DC
Component Over
INV Self-Test Fail
Inverter bridge
damaged or too high
grid harmonics and no
grid-tied condition
1. Wait until the inverter recovers.
2. If the failure persists, please contact the
distributor or after-sales service center.
Phase Lock Fail
INV Over TEMP
The inverter
temperature is higher
than the allowable
upper limit of the
inverter
1. Check whether the temperature of the
radiator displayed on the LCD screen is too
high. If the temperature is too high, wait for a
period of time to recover.
2. Check whether the inverter is at
well-ventilated location.
3. Check whether the inverter is in the direct
Summary of Contents for EAHI-6000-SL-S