inverter will disconnect immediately from the mains power once a fault current with a value
exceeding the limit is detected.
However if an external residual current device (RCD) (type A is recommended) is mandatory.
The switch must be triggered at a residual current of 300 mA (recommended). RCD of other
specifications can also be used according to local standard.
6.3.4 Connection of load end
Tools: inner hex screwdrivers (φ2mm), cable terminals (three-adapter), wire strippers, tape
measures and cables (L, N, PE)
Measure the distance between the
distribution box or the load wiring terminal
and the equipment by the tape measure,
and select the cable with suitable length.
Remove 70mm cable sheath by the wire stripper,
and the 15mm insulating layer of the cable core
by the wire stripper.
Install cables on the parts.
Press the cables and tighten the screws by
0.8+/-0.1Nm torque
Install the plastic core into the main body,
and outward rotate the latch at 15° for
locking.
Place the cable sealing body and the conductor
holder in the slot on the main body, and screw the
cable locking nut into the main body by
2.5+/-0.5Nm torque