15
5.4 Loading
(1) To start the fan:
Click the
[Shift Control]
on
[Control]
menu, or click the icon on the
toolbar into sub-file control interface, power setting and loading. Before loading, first click
[start fan]
.
(2) Loading:
The software has two loading modes: manual loading and automatic
loading.
(3) Manual load:
Can load a single power value, do not select load period in left side,
and directly select the power value on the right side, then click
[Load]
or
[Unload].
If you
want to change the power value, just re-select the power and click
[Load]
or
[Unload].
(4) Automatic loading:
You can set the power and duration of each stage sequentially
for continuous loading. After clicking
[Power Distribution]
,
< Active Power >
column to
set load power,
< Power Factor >
to set power factor, please then click
[OK]
and the
mac
hine will automatically assign load power values. It’s also OK to input load power in
25% and other periods.
Then click
[Interval],
set the duration of each stage, click
[Auto load]
and it
is
automatically loaded. The system will automatically load 25%, 50%, 75%, 100% or 110%,
100%, 75%, 50%, 25% of the sequence, and the power change is completed.
(5) Unload:
Click
[Unload]
to
remove the full load. Please keep the fans running 3-5
minutes after unloading so that standby heat dissipates, then click
[End Task]
to
stop
the fan.