30
Section 5.
Tools
5.5 System Configuration
-allows settings for unique Shelf
components including AC Input physical connections, the physical
configuration, and internal hardware that measures Load Current,
Battery Current, Battery Cell Voltages, and Battery & Rack Temps.
System Configuration page
contains:
•
AC Mode
–
set to match the AC Input to the shelf, either 1Phase 110V or 1Phase 220V.
•
Shelf Configuration
–
set to match the physical Shelf configuration for either:
Main Shelf
(4RU with Control Module and up to 4 Rectifier Modules), or
Extend Shelf
(Main Shelf with 4RU Expansion Shelf for total of 8
Rectifier
Modules
)
•
Symmetry Used
–
set to:
Not Used,
or
Symmetry #1
(mid-string voltage monitored), or
Symmetry #2
(all battery strings voltage-monitored)
•
Battery Temp Sensor
–
Unused
for no external Battery strings;
Used
for any Battery
strings.
•
Rack Temp Sensor
–
set to
Used
and always connect the Rack Temp sensor with the Shelf.
Eagle Eye Power Solutions, LLC | 877-805-3377 | www.eepowersolutions.com