Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 77 / 80
1 = the blind is in upper end position
110
Status lower end position
Output A
DPT 1.011
1 bit
CRT
The blind is reached the lower end position, the device sends information.
The object is;
0 = the blind is not in lower end position
1 = the blind is in lower end position
6.5
Valve Object Description
No
Object name
Name
DTP Type
Length
Flags
95
Control valve HEATING
Control Input
DPT 5.001
1 byte
CW
Via this object, command value for heating operation is sent.
96
Control valve COOLING
Control Input
DPT 5.001
1 byte
CW
Via this object, command value for cooling operation is sent.
97
Toggle Heating/Cooling
Control Input
DPT 1.100
1 bit
CW
If the HVAC System parameter has been selected one control four pipe with switch or
two control two
pipe with switch,
this object is enabled
.
If the parameter
Object value for HEATING the object
is selected 1
:
1 : HEATING
0 : COOLING
If the parameter
Object value for HEATING the object
is selected 0
:
1 : COOLING
0 : HEATING
98
Fault control value
Control Input
DPT 1.005
1 bit
CRT
If the control input telegram does not arrive in the monitoring period, this object set TRUE and send to
bus.
0 : no fault
1 : fault
99
Block
Valve HEATING
Valve COOLING
DPT 1.003
1 bit
CW
This object is used to block the valve operation. The valve does not respond any control input values.
100
Forced operation
Valve HEATING
Valve COOLING
DPT 1.003
1 bit
CW
This object is used to force the valve-desired state. This state can be configure via
Value position on
forced operation in % [0…100]
parameter
.
0 : end of forced operation
1: start of forced operation