Product Manual RCUXXYY 

EAE KNX Room Control Unit

 

            

RCUXXYY PM R1.0 

 

©

EAE Technology 

 

 

www.eaetechnology.com  

 

 

Page 64 / 80 

   

*no 

This parameter can be enabled the direct control. Direct control meaning is control via direct 
communication object. 
 

Starting characteristic of fan 
   

  

yes 

*no 

 

This parameter enables the fan to start from the OFF state with a defined fan speed. The fan can be 
switched on temporarily to a defined switch-on level. This switch-on level can be any of the available 
fan levels. 
 

  Switch on to switch-on level 
   

  1 
  2 

*3 

 

This switch-on level can be any of the available fan levels. 
 

  Minimum dwell period in switch on  
  i

n s [1…65535]

 

  

1…

*5

…65535

 

 

The fan thus remains in the switch-on level until the set dwell time has elapsed. 
 

4.7.2

 

A/B1 - Status Message 

 

Enable communication object  

“Status fan speed x” 1 bit 

 

 

 yes 

*no 

 

Summary of Contents for RCU0800

Page 1: ...EAE KNX Room Control Unit Product Manual RCUXXYY RCU2018 RCU2000 RCU2016 RCU2000 RCU1212 RCU1200 RCU0808 RCU0800 Note RCUXXYY where XX denotes the number of outputs and YY number of inputs...

Page 2: ...20 3 4 1 a Switch Sensor 22 3 4 2 a Switch Dim Sensor 25 3 4 3 a Blind Sensor 26 3 4 4 a Value Forced Operation 29 3 5 Enable Output A J 32 3 6 Switch 34 3 6 1 A1 General 34 3 6 2 A1 Function 36 3 6...

Page 3: ...3 A Function 59 3 8 4 A Limit 61 3 9 Fan Coil 62 3 9 1 Fan 62 3 9 2 A B1 Status Message 64 3 9 3 A B1 Automatic Operation 66 3 9 4 A B1 Direct Mode 67 4 Function Chart 68 5 Object Description 69 5 1...

Page 4: ...d as 5 4 3 2 independent output channels for XX 20 16 12 8 respectively Each channel can be configured to have different modes of operation as follows Suitable for switching resistive capacitive and i...

Page 5: ...ic drivers 1500 W Type of contact Potential free bistable Input Number YY binary inputs Scanning voltage 5 V pulsed Current 1 mA Cable length 300 m Installation 35mm mounting rail EN 60 715 Operating...

Page 6: ...length 300 m Installation 35mm mounting rail EN 60 715 Operating elements LED red and button For physical address Temperature range Ambient 5 C 45 C Storage 25 C 55 C Humidity max air humidity 85 no...

Page 7: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 6 80 1 3 Connection Example RCU2018 Connection Example 1 Connection Example 2...

Page 8: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 7 80 RCU0808 Connection Example 3 Connection Example 4...

Page 9: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 8 80 RCU1212 Connection Diagram 5 Connection Diagram 6...

Page 10: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 9 80 RCU1616 Connection Diagram 7 Connection Diagram 8...

Page 11: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 10 80 1 3 Scale Drawings RCUXXYY RCU2018 RCU1616...

Page 12: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 11 80 RCU1212 RCU0808...

Page 13: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 12 80 Scale Dimensions RCUXXYY...

Page 14: ...d Frost alarm 1 005 1 bit CWTU 5 Input a Disable 1 003 1 bit CW 6 Input a Switch 1 001 1 bit CWT Switch short 1 001 1 bit CWT Shutter Up Down 1 008 1 bit CT Value 0 1 1 001 1 bit CWT Value forced 2 00...

Page 15: ...Move to position 1 2 1 022 1 bit CW Fan A B1 Status fan ON OFF 1 001 1 bit CT Valve HEATING Forced operation 1 003 1 bit CW 101 Output A1 Forced positioning 2 001 2 bit CW Output A Output A B Move to...

Page 16: ...G Status valve purge 1 003 1 bit CRT 108 Output A2 External logic input 1 001 1 bit CW Output A Output A B Status slat 0 255 5 001 1 byte CRT Valve COOLING Status valve position 1 001 1 bit CRT Status...

Page 17: ...m is not received device may be defective or KNX cable can be disconnected If parameter is selected yes following parameters come up In operation bit 0 1 Telegram value can be selected as 1 or 0 In op...

Page 18: ...2 Wind 3 Frost 1 Rain 2 Frost 3 Wind 1 Frost 2 Wind 3 Rain 1 Frost 2 Rain 3 Wind If an alarm is triggered the drives move into a safe position and stay in safe position until the event is over You can...

Page 19: ...is damaged and the blind moves into the parameterized position 0 If 0 is selected cyclically monitoring is deactivated If the alarm telegram value is 1 weather alarm is activated Frost alarm disable e...

Page 20: ...1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x8A 138...

Page 21: ...1 x blind scene parameters mean blind height and slat position If the blind type is selected roller shutter slat position parameter is invalid 0 open blind 100 bottom blind also you can select between...

Page 22: ...rt long operation and cyclical sending This parameter is selected switch dim sensor Start stop dimming and stepwise dimming are possible This parameter is selected shutter sensor For movement louvre a...

Page 23: ...ation objects Debounce Bouncing is the tendency of any two metal contacts in an electronic device to generate multiple signals as the contacts close or open debouncing is any kind of hardware device o...

Page 24: ...a short or long operation Connected contact type normally closed normally open This parameter is visible if there is distinction between short and long operation The contact type of the push button a...

Page 25: ...determines the switching value to be sent when the contact is short press Reaction on long operation ON OFF TOGGLE no reaction This parameter is visible if there is distinction between short and long...

Page 26: ...ere Dimming functionality Dimming and switching Only dimming This parameter is select Dimming and switching If the dimming actuator was switched on by a short push button action then it is dimmed brig...

Page 27: ...dition button releases than STOP dimming telegram sends Cyclic sending telegram is not necessary in this case Dimming steps The dimming telegram is sent cyclically during a long operation STOP telegra...

Page 28: ...amella In additional it stops a running movement of the shutter Long operation Shutter up Shutter down Long press is opposite direction to the last movement for moving the shutter up or down 1 button...

Page 29: ...e property with two switches 2 switch operation moving shutter On operation The property object Shutter is choose and performs the up and down movement of the shutter The direction of movement depends...

Page 30: ...efinitely pressed 4 2 4 a Value Forced Operation You can use these value forced functions to parameterize different object actions You can transmit one or two objects short or long press status sequen...

Page 31: ...n 1 byte value 0 255 2 byte 32768 32767 2 byte 0 65535 4 byte floating point 4 byte value 0 4294967295 This parameter is visible distinction short long operation when button is pressed this value send...

Page 32: ...time factor between 1 255 Transmit object value after bus voltage recovery yes no This parameter is visible no distinction short long operation In the event of power supply failure to the electronics...

Page 33: ...s are combined into one blind channel In the blind mode four relay are locked against each other The DC blind can be used to control electrically driven blinds shutters awnings and venetian blinds DC...

Page 34: ...ch Output group B shutter blind AC 2 x switch The appropriate output pair is configured by this parameter Set the parameter to shutter blind AC blind The appropriate output pair is configured to AC bl...

Page 35: ...tch state on 1 relay contact open Normally open contact Switch state off 0 relay contact open Switch state on 1 relay contact closed Send switch status feedback telegram no after change after request...

Page 36: ...tact The relay contact open or close after bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state...

Page 37: ...Y PM R1 0 EAE Technology www eaetechnology com Page 36 80 4 4 2 A1 Function Above function can be set for each channel This function I Staircase function II External logic III Forced position IV Sweep...

Page 38: ...c 0 5 240 min 0 59 sec Staircase function on time is calculated by duration of staircase lighting Staircase lighting time is defined by this parameter At the end of the on time the relay off or active...

Page 39: ...ter is selected yes receive Permanent ON communication object after restart staircase function Activate pre warning time yes no The warning function can be activated by this parameter select yes Then...

Page 40: ...ect value 1 and External logic input object value 0 relay switch as a result of 1 0 operation External logic function type AND OR XOR This parameter selects the type of logic function between Switch a...

Page 41: ...is desired to warn a person that lights will go out shortly Send counter value 1 3 10 The lamps connected to the relay will be switched off as many times Enter the number of how many blink doing in th...

Page 42: ...Product Manual RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 41 80 4 4 2 4 A1 Scene For more information please look scene page 12...

Page 43: ...nication object and parameters for the respective outputs differ on the mode of operation The ETS adapts the parameters and communication object for all group Set the parameter to venetian blind In th...

Page 44: ...l to an approach position specified by other parameters Other parameters are Position height in 0 100 0 top 100 button Position slat in 0 100 0 top 100 button This parameters are configured the blind...

Page 45: ...ow that the drive uses for the movement from lower to the upper position The device is measured the travel time with current detection Than up down movements are stored Set the parameter to set travel...

Page 46: ...re travel detection If the Detect travel times Up Down is selected set travel times this parameters are visible This parameter is configured the blind position after the reference movement The step or...

Page 47: ...etermine times for slat via duration of slat adjustment step via total duration for slat turning This parameter defines the slat moving time configuration Duration to turn slat from 0 100 in ms 50 600...

Page 48: ...n lower end position 100 disable 0 100 The blind will set the slat according to the parameterized value after the end position is reached This parameter is valid for move up down communication object...

Page 49: ...e limit position 0 means the blind fully up or slat closed up 100 means the blind fully down or slat closed down Enable communication objects Move to set position1 4 1 bit no yes If the parameter sele...

Page 50: ...0 80 100 Position 4 Slat in 0 100 0 top 100 bottom 0 80 100 These parameters define the blind preset height slat position Slat positions are only visible when the blind type is selected Venetian blind...

Page 51: ...Assignment to frost alarms yes no There are three different wind alarms available These alarms can be used for instance to protect Venetian blind or awning The blind is also assigned to multiple wind...

Page 52: ...al position Individual position can be set this parameters Position height in 0 100 0 top 100 button Position slat in 0 100 0 top 100 button This parameters are configured the blind height and slat po...

Page 53: ...time It can protect the person for unexpected accident Bit 1 Bit 0 Function 0 x Forced position not active normal control 0 x Forced position not active normal control 1 0 Forced position active rais...

Page 54: ...tion function can be initialized after bus voltage return so the forced operation communication object is updated After the bus voltage return forced position function set to the parametrized position...

Page 55: ...transmit mode after change after request after change or request This parameter is selected the communication object transmit mode which means object flag is adjusted Upper and lower end position stat...

Page 56: ...communication object Set the parameter to two control two pipe In this system contains only HEATING exchangers 2 pipes is used for HEATING or COOLING Both objects are used to for HEATING valve The las...

Page 57: ...be monitored cyclically The device then expect a telegram from the thermostat within the cycle time Send object value Control value fault 1 bit no after change after request after change or request I...

Page 58: ...possibility of inversion the switching state If the valve control parameter is selected two point on off this parameter is visible Observe reversing time no 100 ms 300 ms 500 ms 700 ms 1000 ms This p...

Page 59: ...to 100 if the valve is adjusted to the opening direction on the 101st adjustment then the automatic adjustment is not executed if to the closing direction the automatic adjustment will be executed and...

Page 60: ...is unblocked again 0 The blocking is triggered by sending a logical 0 at the belonging block object Only through sending a logical 1 the channel is unblocked again Enable communication object Forced...

Page 61: ...or can protect the valves for heating and cooling connected for each channel against sticking The anti sticking protection is generally necessary to prevent a valve defect if the valve drives are not...

Page 62: ...00 The parameter adjust the minimum limit of the control value Min limit of valve position 0 100 0 100 The parameter adjust the minimum limit of the valve position Max limit of control value 0 100 0 1...

Page 63: ...the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels only one fan output switches fan outputs switch hierarchi...

Page 64: ...is visible This parameter is used to configure the fan delay time This time is using between the fan speed switching Fan speed on bus voltage failure unchanged off 1 2 3 Using this parameter the fan r...

Page 65: ...to start from the OFF state with a defined fan speed The fan can be switched on temporarily to a defined switch on level This switch on level can be any of the available fan levels Switch on to switch...

Page 66: ...the object send type Enable communication object Status fan speed 1 byte yes no The data format for the fan level feedback is defined as 1 byte Meaning current fan speed required fan speed Current fa...

Page 67: ...1 0 1 automatic operation is activated by a telegram with value 1 0 automatic operation is inactivated by a telegram with value 0 Threshold value OFF speed 1 In 0 100 0 10 100 Threshold value speed 1...

Page 68: ...d as 1 bit Separate three objects are defined separately for each fan level If several ON OFF telegrams are received consecutively in a short period of time at various communication objects Fan speed...

Page 69: ...Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 68 80 5 Function Chart The following schematic indicates the function sequence The functions are processed Communication object enter th...

Page 70: ...Blind Actuator C 0 recall scene 1 store scene R Reserved The object to recall and store the scene 1 64 is sent via the group address 8 bit scenes are stored in the Switch Blind Actuator Scene recall...

Page 71: ...ect name Name DTP Type Length Flags 5 Disable Input a DPT 1 003 1 bit CW 0 enable input 1 disable input This object is only visible if it is used as an input Via the group address linked to this objec...

Page 72: ...it CT 0 OFF 1 ON Switching telegrams for long push button press are sent via the group address linked with this object if the parameter Number of objects for short long operation is set to 2 object 7...

Page 73: ...button options 0 No Upper end limit 1 Upper end limit 8 Value temperature Input a DPT 14 068 32 bit CT The value type is selected floating point this object is created For more information look Value...

Page 74: ...tion is working back ground of the Permanent ON If the Permanent ON object is set to off the other function switch result can be visible on the output After bus voltage return the object is deactivate...

Page 75: ...velling range parameter Blind up or down end position can be limited by this communication object The blind stops automatically when the configured upper or lower end position have been reached After...

Page 76: ...received 0 the current position is stored as the new position 1 or 3 If the telegram value is received 1 the current position is stored as the new position 2 or 4 The object is 0 set to position 1 or...

Page 77: ...peration enable 2 forced active move UP operation disable 3 forced active move DOWN operation disable 107 Status height 0 255 Output A DPT 5 001 1 byte CRT The blind position of drive is available as...

Page 78: ...100 1 bit CW If the HVAC System parameter has been selected one control four pipe with switch or two control two pipe with switch this object is enabled If the parameter Object value for HEATING the o...

Page 79: ...nfigured 1 bit 0 valve position is zero 1 valve position is not zero If the object is configured 1 byte 0 255 valve position is show via percentage 6 6 Fan Object Description No Object name Name DTP T...

Page 80: ...eed 1 Fan DPT 1 001 1 bit CRT 103 Status fan speed 2 Fan DPT 1 001 1 bit CRT 104 Status fan speed 3 Fan DPT 1 001 1 bit CRT Only visible if the Enable communication object Status fan speed x 1 bit is...

Page 81: ...RCUXXYY EAE KNX Room Control Unit RCUXXYY PM R1 0 EAE Technology www eaetechnology com Page 80 80 107 Status automatic Fan DPT 1 003 1 bit CW The object indicates the status of the automatic mode 0 in...

Reviews: