Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 50 / 80
4.5.4.2
A/B
–
Weather alarm
The weather functions must first be globally enabled before they can be parameterized and used.
After general weather function is enabled, the weather alarm can be enabled or disabled
i
ndependently of one other. The reaction at beginning of an alarm telegram is received “1”. Alarm
function is terminated as soon as a new alarm telegram is received “0”.
Assignment to wind alarms
Assignment to rain alarms
Assignment to frost alarms
yes
*no
There are three different wind alarms available. These alarms can be used for instance, to protect
Venetian blind or awning. The blind is also assigned to multiple wind alarm. The three wind alarms
have the same priority. These are respect to one other with logic OR.
Behavior in case of wind alarm
Behavior in case of rain alarm
Behavior in case of frost alarm
*no reaction
up
down
stop
position 1
position 2
position 3
position 4
individual position
When the alarm is activated, the blind moves this position.
▪
Set the parameter to “
no reaction
”;
At the beginning of the wind alarm, the relay of blind shows no reaction. Any movements in
progress at instant will still be completely finished.
▪
Set the parameter to “
up
”;