Send object type
*no
after a change
after request
after change or request
This parameter defines the object send type.
4.7.3
A/B1 - Automatic Operation
Object value “automatic ON/OFF”
switch on to automatic
*1
0
1: automatic operation is activated by a telegram with value 1
0: automatic operation is inactivated by a telegram with value 0
Threshold value OFF <--> speed 1
In % [0…100]
0…
*10
…100
Threshold value speed 1 <--> speed 2
In % [0…100]
0…*30…
100
Threshold value speed 2 <--> speed 3
In % [0…100]
0…*70…100
A fan level switches on when its command value lower limit is reached or exceeded.
Hysteresis threshold
Value in % +/-
[0…20]
0…
*5
…20
The fan level switches off again as soon as its command value lower limit minus the hysteresis is
undershot again.