Document No. BExL25D and BExL15D Norwegian    Issue E       (Two Sheets)     12-02-10                                                                               (19)

 

INSTRUKSJONSHÅNDBOK  (ATEX IECEx)  (NOR) 

BExL25D og BExL15D 

Flammesikre 

høyttalerne 

 
 
 
 

 
 
2)   Merking 

 
Alle enheter har en etikett med følgende viktige informasjon: 

 
Enhetstypenr.      

BExL25D   eller   BExL15D

 

 

Impedans:     

8 ohm eller 16 ohm 

100V eller 70V Lijne

 

 
Kode:   

Ex d IIC T4 for Ta –50°C to +55°C 

        

Ex d IIB T4 for Ta –50°C to +70°C 

 

Sertifikat nr.

    

KEMA 99ATEX6312 

 

 

IECEx KEM 10.0003

 

 

        

 

 

 

 
 

Advarsler: 

 

MÅ IKKE ÅPNES I EKSPLOSIV  

 

 

 

      GASSATMOSFÆRE 

 

      

DEKKEBOLTER KLASSE A4-80 

 
BRUK VARMEBESTANDIGE KABLER OG  
KABELMUFFER (godkjent for 110 ºC) VED 
 OMGIVELSESTEMPERATURER OVER 40 ºC 

 

4)   Installasjonskrav 

 

Høyttalerne må installeres i samsvar med følgende eller 
tilsvarende standarder. 

 
EN 60079-14:2008 

Elektriske installasjoner i farlige

 

IEC60079-14:2007 (Ed4)

    områder (unntatt gruver)

 

 
EN 60079-10:2003 

Klassifisering av farlige områder

 

IEC60079-10:2008 (Ed1) 
 

Installering må kun utføres av kompetente personer, og alle 
gjeldende lokale bransjestandarder må overholdes. 

 

5)  Soner, gassgruppe, kategori og temperatur 
     klassifisering 

 
Enhetene kan installeres på steder med følgende forhold: 

  

Områdeklassifisering: 

 

Sone 1 

Eksplosiv gass/luft-blanding som sannsynligvis 
forekommer ved normal drift. 

Sone 2 

Eksplosiv gass/luft-blanding som ikke vanligvis 

vil forekomme, og om den gjør det, kun vil 
forekomme i kort tid. 

 
 

 

  
 
 

 
 
 
Gassgrupperinger: 

 

Gruppe IIA 

Propan 

Gruppe IIB 

Etylen 

Gruppe IIC  < +55ºC 

Hydrogen og acetylen 

  

Utstyrskategori:

 2G 

 

Temperaturklassifisering: 

 

T1 

400 

o

C  

T2 

300 

o

T3 

200 

o

T4 

135 

o

 

Omgivelsestemperaturområde: 

 

  

-50 

°

C til +55 

°

C Gassgrupperinger IIA, IIB og IIC 

-50 

°

C til +70 

°

C Gassgrupperinger IIA og IIB 

 

6)  Plassering og montering av høyttalerne 

 
Se tegningen. A 
 

7)  Sikkerhetsvarsel (elektrostatisk fare)

 

 

Lydhorndelen  er  laget  av  ABS-plast.  For  å  unngå  mulig 
ELEKTROSTATISK  LADNING  må  enheten  derfor  kun 

rengjøres med fuktig klut. 

 
8)  Tilgang til flammesikkert hus

 

 

Se tegningen. B 

 
Merk: De fire 

M6-skruene er av rustfritt stål klasse A4-80, 

og  kun  skruer  i  denne  kategorien  kan  brukes  til  disse 
lydalarmene. 

Derfor  er  det  viktig  at  disse  skruene  med 

tilhørende  fjærskiver  oppbevares  på  et  sikkert  sted  under 

installeringen. 

 
9)  Effektforsterkervalg 
  

Det er viktig at høyttalerne er koplet til effektforsterkere som 

har  utganger  som  er  kompatible  med  typen  høyttalere  som 
benyttes.  Høyttalere  med  100V  eller  70V  linjematchende 

transformator  må  kobles  til  effektforsterker  med  100V  eller 
70V linjeutgang. Høyttalere med lav impedans 8 ohm eller 16 

ohm må kobles til forsterkere med egnet lavimpedanseffekt. 
Ved  valg  av  kabelstørrelse  må  en  ta  hensyn  til  strømmen 

som hver enhet bruker, antall høyttalere på linjen og lengden 
på kabelsengene. 
 

Tabellen nedenfor viser området for høyttalerne: 

 

Enhetstype 

Inn  

 

Watt 

 

Maks 

 

 

 

 

 

 

I/P volt

 

BExL25D  

100 V linje 

25 W 

 

100 V 

BExL25D  

70 V linje  

25 W 

 

70 V 

BExL25D  

8 ohm 

 

25 W 

 

14,14 V 

BExL25D  

16 ohm   

25 W 

 

20 V 

0518 

II 2G 

CE-merking: 

Varslet organ nr. 
 

Epsilon x: 

Utstyrsgruppe og –
kategori:

 

 

Summary of Contents for BExL25D

Page 1: ...C Year of Construction Serial No i e 10 1L23000001 3 Type Approval Standards The loudspeakers have EC Type Examination and IECEx certificates issued by KEMA and have been approved to the following st...

Page 2: ...n place W hen replacing the flameproof cover casting ensure that it is square with the flameproof chamber casting before inserting Carefully push the cover in place allowing time for the air to be exp...

Page 3: ...hen the cable entry temperature may exceed 70 C and therefore suitable heat resisting cable glands must be used with a rated service temperature of at least 110 C If a high IP Ingress Protection ratin...

Page 4: ...citor and this should be taken into account when selecting the value of the end of line monitoring resistance The end of line monitoring resistor can be connected across the terminals on the end of li...

Page 5: ...y to occur and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Up to 55 C only Hydrogen and Acetylene Equipment Category 2G Temperature Clas...

Page 6: ...ds Only cable glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60...

Page 7: ...roef aandraaien om vast te zetten Serrer la vis pour une fixation s re Zum Sichern Schraube anziehen Stringere la vite per il fissaggio Stram skruen for feste Aperte o parafuso para fixar Apriete el t...

Page 8: ...td Impress House Mansell Road Acton London W3 7QH sales e 2 s com Tel 44 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No BExL25D and BExL15D English Issue E Four Sheets 12 02 10 8 Wirin...

Page 9: ...synligvis ikke og hvis det sker vil det kun v re for en kort tidsperiode Gasgrupperinger Gruppe IIA Propan Gruppe IIB Ethylen Gruppe IIC 55 C Hydrogen og acetylen Udstyrskategori 2G Temperaturklassifi...

Page 10: ...es samt opfylde kravene i Ex d standard for flammesikker installation EN60079 14 2008 IEC60079 14 2007 SIKKERHEDSADVARSEL Hvis de h jtydende BExL25D h jttaler anvendes ved h je omgivende temperaturer...

Page 11: ...2 Ontplofbaar gas luchtmengsel is onwaarschijnlijk en indien dit ontstaat zal het waarschijnlijk slechts korte tijd aanwezig blijven Gasgroeperingen Groep IIA Propaan Groep IIB Ethyleen Groep IIC 55 C...

Page 12: ...rtels worden gebruikt die zijn goedgekeurd voor Ex d toepassingen geschikt zijn voor het bekabelingstype dat wordt gebruikt en voldoen aan de vereisten van de norm EN60079 14 2008 IEC60079 14 2007 ten...

Page 13: ...normale Zone 2 M lange d air et de gaz explosif ne pouvant pas survenir et qui dans le cas contraire serait pr sent que tr s bri vement Groupes de gaz Groupe IIA Propane Groupe IIB Ethyl ne Groupe IIC...

Page 14: ...cations Ex d peuvent tre utilis s et ils doivent tre ad quats pour le type de c ble utilis et r pondre aux exigences d installation d antid flagrant Ex d de norme EN60079 14 2008 IEC60079 14 2007 AVER...

Page 15: ...Luft Mischung vorliegen Zone 2 Explosive Gas Luft Mischung unwahrschein lich und sollte sie doch auftreten dann nur kurzfristig Gasgruppen Gruppe IIA Propan Gruppe IIB thylen Gruppe IIC 55 C Wasserst...

Page 16: ...abeltyp geeignet sein und zudem den Anforderungen der Ex d Norm zur Installation schwer entflammbarer Ger te EN60079 14 2008 IEC60079 14 2007 entsprechen SICHERHEITSHINWEIS Wenn die BExL25D High Outpu...

Page 17: ...esplosivo durante il normale funzionamento Zona 2 Non probabile che sia presente gas esplosivo e se esso dovesse essere presente potr esserlo solo per un breve periodo di tempo Gruppi di gas Gruppo I...

Page 18: ...ngressi per premistoppa con filettature M20 x1 5 Utilizzare solo premistoppa approvati per le applicazioni Ex d essi inoltre devono essere adeguati al tipo di cavo in uso e devono rispettare gli stand...

Page 19: ...losiv gass luft blanding som ikke vanligvis vil forekomme og om den gj r det kun vil forekomme i kort tid Gassgrupperinger Gruppe IIA Propan Gruppe IIB Etylen Gruppe IIC 55 C Hydrogen og acetylen Utst...

Page 20: ...elmuffer godkjent for Ex d bruk kan brukes og de m v re egnet for typen kabel som brukes samt overholde kravene i standarden for Ex d flammesikker installering EN60079 14 2003 IEC60079 14 2007 SIKKERH...

Page 21: ...va em funcionamento normal Zona 2 Improbabilidade de ocorr ncia de mistura gasosa explosiva mesmo que tal ocorra s ser por per odo curto Grupos de gases Grupo IIA Propano Grupo IIB Etileno Grupo IIC 5...

Page 22: ...ara aplica es prova de explos o que devem ser adequados ao tipo de cabo a ser usado e satisfazer tamb m os requisitos da norma EN60079 14 2008 IEC60079 14 2007 relativa instala o prova de fogo e de ex...

Page 23: ...s posible ocurra durante el funcionamiento normal Zona 2 Mezcla explosiva improbable de aire y gas que de producirse lo har s lo por breve tiempo Grupos de gas Grupo IIA Propano Grupo IIB Etileno Grup...

Page 24: ...cable aprobados para aplicaciones Ex d los cuales deben ser adecuados para el tipo de cable que se est utilizando adem s de satisfacer los requisitos de la norma EN 60079 14 2008 IEC60079 14 2007 para...

Page 25: ...al drift Zon 2 Explosiv gasblandning f rv ntas f rekomma s llan och d endast kortvarigt Explosionsgrupper Grupp IIA Propan Grupp IIB Etylen Grupp IIC 55 C V te och acetylen Kategori p utrustning 2G T...

Page 26: ...kabeling ngar med M20 x 1 5 g nga Endast kabelgenomf ringar godk nda f r Ex d bruk f r anv ndas Dessa m ste passa den typ av kabel som anv nds och dessutom uppfylla kraven f r explosionst t kapsling E...

Page 27: ...004 Directive 89 106 EEC Construction Products Directive CPD BExS110D24DC BExS120D24DC tones 2 3 9 15 16 17 only Notified Body for EC type Examination VdS Schadensverh tung GmbH Notified Body No 0786...

Reviews: