User Manual HTS801
Humidity and Temperature Sensor for High Humidity and Chemically Polluted Conditions | 42
INT16
Measurand
Unit
Scale
3)
Register number
1)
[DEC]
Register address
2)
[HEX]
Read.register:.function.code.0x03./.0x04
Relative humidity
%
100
4011
FAA
Temperature
°C
100
4002
FA1
Temperature
°F
50
4003
FA2
Temperature
K
50
4005
FA4
Dew point temperature
°C
100
4053
FD4
Dew point temperature
°F
100
4054
FD5
Dew point temperature
K
100
4074
FE9
Frost point temperature
°C
100
4066
FE1
Frost point temperature
°F
100
4067
FE2
Frost point temperature
K
100
4075
FEA
Absolute humidity
g/m
3
10
4057
FD8
Absolute humidity
gr/ft
3
10
4058
FD9
Mixing ratio
g/kg
10
4061
FDC
Mixing ratio
gr/lb
10
4062
FDD
Wet bulb temperature
°C
100
4055
FD6
Wet bulb temperature
°F
100
4056
FD7
Wet bulb temperature
K
100
4073
FE8
Specific enthalpy
kJ/kg.
1
4063
FDE
Specific enthalpy
BTU/lb
1
4064
FDF
Specific enthalpy
ft.lbf/lb
1
4065
FE0
Water vapour partial pressure
mbar
10
4051
FD2
Water vapour partial pressure
psi
1000
4052
FD3
Ice bulb temperature
°C
100
4119
1016
Ice bulb temperature
°F
100
4120
1017
Ice bulb temperature
K
50
4121
1018
Specific humidity
g/kg
10
4124
101B
Specific humidity
gr/lb
10
4125
101C
1) Register number starts from 1
2) Register address starts from 0
3) Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.
Tab. 9
HTS801 FLOAT32 and INT16 measured data registers
6.2.3.
Freely Configurable Custom Modbus Map
It.is.possible.to.map.measured.value/status.registers.arbitrarily.in.a.block.with.up.to.20.registers.provided.for.
this purpose. This means that registers of interest may be mapped in an area with consecutive registers, so that
important values can be queried with a single command in one block.
The custom map can be configured via:
▪.
PCS10 Product Configuration Software and the USB configuration cable HA010327.
The PCS10 can be downloaded free of charge from
.
▪.
Modbus protocol commands, refer to the example in chapter 6.3 Modbus RTU Example.
The register block for the configuration of the customisable Modbus map consists of the registers 6001 (0x1770)
to 6010 (0x1779). For the blockwise query of the measured values behind Modbus registers 3001 (0xBB8) to
3020 (0xBCB), the firmware accesses this configuration area and thus gets the information which measured
value/status.registers.are.to.be.output..A.maximum.of.10.user-defined.registers.can.be.mapped..The.table.below.
shows an example: