9
Normal Mode Rejection:
60 dB at 50 or 60 Hz
Accuracy:
Volt range: +/- (1 mV + 0.25% of measurement)
mA range: +/- (250 µA + 0.25% of measu shunt
resistor accuracy)
Temperature Drift:
Less than 200 ppm
Power Supply Options:
85 to 264Vac or 24Vac or dc, -15% +20%
Operating Altitude:
up to 2000 meters
Operating Temperature Range: 0 - 55
Q
C
Storage Temperature:
-30
Q
C to 70
Q
C
Operating Humidity Range:
5 - 85% RH non-condensing
Vibration :
10 to 150 Hz at a peak of 1G
Inter unit Spacing:
The recommended minimum spacing between
controllers shown here should not be reduced to allow
sufficient natural air flow 1.5” (38mm).
Cable Size:
For supply connections use 16AWG or larger wires
rated for at least 75
Q
C. Use copper conductors only. For
24Vdc the polarity is not important. It is the User’s
responsibility to provide an external fuse or circuit breaker.
Input Protection:
Internal thermistor
Fusing for 85/265Vac fuse type T rated 1A 250V
For 24Vac/dc fuse type T rated 4A 250
4.2.2 Linear Input specifications
Input:
0 - 5Vdc, 1 - 5 Vdc, 0 - 10Vdc, 2 - 10Vdc
0 - 20mA, 4 - 20mA (by external 2.49
R
resistor
across rear terminals) Thermocouple & RTD
Input Span:
milliampere: 0 - 20mA +/- 27%
Volts:
-0.2V to 12.7V
Input Impedance:
Greater than 200K
R
Linear
Volt Ranges
Input Impedance
Greater than 1M
R
Linear
millivolt Range