18
Display Units “
Un
”
This parameter selects the temperature unit to display
Selections: °C or °F or Off = None
Default:
°C
Decimal Point Position “
_ _ _ _ . _
”
This parameter selects the decimal point position
Selections:
_ _ _ _ _
for no digits after the decimal point
_ _ _ _ . _
for one digit after the decimal point
_ _ _ . _ _
for two digits after the decimal point
_ _ . _ _ _
for three digits after the decimal point
_ . _ _ _ _
for four digits after the decimal point
Default
: _ _ _ _ . _
Full Scale Readout
“
F.S.U.
”
This parameter establishes the Full Scale Value
The display alternates between F.S.U. (Full Scale Value) and a numerical value from 10 to
99990. Only the numerical value is shown during modification.
Default:
1200.0
Low Scale Readout “
L.S.U.
”
This parameter establishes the Low Scale Value
The display will alternate between L.S.U. (Low Scale Value) and a numerical value from 0 to
99990. This parameter establishes the display reading at the “zero” input (i.e., 4 mA input =
350).
Default:
_210.0
Display Filter Time Constant “
F.t.C.
”
This parameter selects the Filter Time Constant.
.4
for 400 millisecond filter time constant
1
for 1-second filter time constant
2
for 2 second filter time constant
3
for 3 second filter time constant
4
for 4 second filter time constant
5
for 5 second filter time constant
Default:
.4mS
Input Failsafe “
IFS
“
HI
input fails high with sensor break
Lo
input fails low with sensor break
no
disabled
Default:
HI