17
F
ig 8.1.3-4
8.1.4 Configuration, Calibration Mode
To enter the configuration mode, hold the
FUNC
button while powering the unit on until
COnF
is
displayed. A list of all configuration parameters starts.
•
Press
FUNC
to initiate the configuration procedure, starting at the first parameter.
•
Press
RESET
to initiate the configuration procedure, starting with the last parameter.
•
Press to toggle the display from
COnF
to
CAL,
initiating output calibration mode, if required.
For each parameter you will either select one of several choices or enter a numerical value.
•
Press to modify or change the parameter or increase the number displayed.
•
Press to modify or change the parameter or decrease the number displayed.
•
Press
FUNC
to save your changes and step to the next parameter.
•
Press
RESET
to step to the previous parameter without saving your changes.
8.1.5 Configurable Parameters
The following is the complete sequence of configurable parameters in the configuration mode
(
COnF
). Once the parameter is displayed, the used can toggle though various options from
which to select. Display in digital LCD font.
Input Type “
I
P
”
This parameter selects the type of input that will be used.
Selections:
J, K, E, L, N, R, S, T, Pt100rd, 0.20, 4.20, 0.5, 1.5, 0.10, 2.10
Default:
J
Note: 2.49
R
resistor is required for 0 (4) - 20 mA inputs.