Tower ESS Unit User Manual
14
3 Installation and Configuration
3.1 Environmental Requirement
3.1.1 Cleanliness
The battery system has high voltage connectors. The environment condition will affect the
isolation performance of the system.
Before installation and system power on, the dust and iron scurf must be removed to keep a
clean environment. And the environment must have certain anti-dust ability.
Dust and humidity condition shall be periodic checked during the system continuous operation.
3.1.2 Temperature
Tower system working temperature range: 0
℃
~50
℃
; Optimum temperature: 18
℃
~30
℃
;
Caution:
Out of the working temperature range will cause the battery system over / low
temperature alarm or protection which may lead to the cycle life reduction.
3.1.3 Cooling System
It is essential to equip a cooling system to keep the battery system in a relevant temperature
range.
Caution:
Out of the working temperature range will cause the battery system over / low
temperature alarm or protection which may lead to the cycle life reduction.
3.1.4 Heating System
It is essential to equip a heating system to keep the battery system in a relevant temperature
range. If the environment is lower than 0
℃
,the system may be shut down for protection
purpose.
It is necessary to open the heating system at first.
Caution:
Out of the working temperature range will cause the battery system over / low
temperature alarm or protection which may lead to the cycle life reduction.
3.1.5 Fire-extinguisher System
The room must be equipped with fire-extinguisher system for safety purpose.
The fire system
needs to be regularly checked to be in normal condition. Refer to the using and maintenance
requirements, please follow local fire equipment guidance.
3.1.6 Grounding System
Make sure the grounding point for battery system is stable and reliable before the battery
installation. If the battery system is installed in an independent equipment cabin(e.g. container),
must make sure the grounding of the cabin is stable and reliable.
The resistance of the grounding system must
≤
100m
Ω
3.2 Installation clearance requirements
Please note that the battery should be installed with a minimum safe clearance from the
surrounding equipment or battery. Please refer to the minimum clearance diagram below.