Diamond 36kW Manual
Dynatronix, Inc.
198-1600-00 Rev F
Page 11 of 146
4. Product Specifications
PRODUCT SPECIFICATIONS
INPUT POWER
INPUT PROTECTION
Main:
MODEL
MAXIMUM
INPUT CURRENT
RECOMMENDED FUSE
RATING
(NOT INCLUDED)
DHP12-1500
33A @ 380VAC
50A
27A @ 480VAC
40A
63A @ 200VAC
100A
53A @ 240VAC
80A
DHP12-3000
66A @ 380VAC
100A
53A @ 480VAC
80A
126A @ 200VAC
190A
105A @ 240VAC
160A
DHP24-750
32A @ 380VAC
50A
26A @ 480VAC
40A
61A @ 200VAC
90A
51A @ 240VAC
80A
DHP24-1500
65A @ 380VAC
100A
50A @ 480VAC
75A
122A @ 200VAC
200A
102A @ 240VAC
150A
DHP48-375
32A @ 380VAC
50A
26A @ 480VAC
40A
61A @ 200VAC
90A
51A @ 240VAC
80A
Note: Input current and fusing is listed for the entire system. If desired, individual modules within a system
could be wired separately and fuses could be installed for each module.