BlueWave® MX-MIM User Guide
21
PROFINET
Table 5. PROFINET IO Server Configuration (Defaults Highlighted)
Slot #
Name
CIP Data Type
1
Module 0x31 (Input) Cont 4 Emitters
See
Table 7Table 7 for bytes 0 to 115
SINT[116]
2
Module 0x41 (Output) Cont 4 Emitters
See Table 6 for bytes 0 to 7
SINT[8]
Table 6. Output Slot Definition
Byte
Data
Type
Description
(Command
–
Field)
Value Reference
0
BYTE
Set Emitter LED State
Bit 0: Emitter 1
…
Bit 3: Emitter 4
Turn Emitter LED ON/OFF
Bit set to 1 == ON
Bit set to 0 == OFF
1
SINT
Reset Unit
Transition From 0 to 1 Will Reset
the Unit
2
SINT
Reset Alarms
Transition From 0 to 1 Will Reset
Alarm State
3
SINT
Reserved
4
SINT
Set Emitter 1 Power Level
–
Power Level
Set Emitter 1 Power Level (1-100)
5
SINT
Set Emitter 2 Power Level
–
Power Level
Set Emitter 2 Power Level (1-100)
6
SINT
Set Emitter 3 Power Level
–
Power Level
Set Emitter 3 Power Level (1-100)
7
SINT
Set Emitter 4 Power Level
–
Power Level
Set Emitter 4 Power Level (1-100)