10
BlueWave® MX-MIM User Guide
Installation
DIN Rail Mounting (Grounded)
1.
Position the unit below the 35mm DIN rail, with the top tilted slightly outwards, then
lift upwards until the bottom of the DIN rail clip is engaged. (Figure 6)
2.
Tilt top of the unit back until the DIN rail rests in the clip, then release. The clips are
spring loaded so they will pull the unit downward slightly and engage the rail.
(Figure 7)
NOTE:
1-inch minimum distance on clearance of vents. The DIN rail must also be
grounded.
Figure 6. DIN Rail Mounting
–
Step 1
Figure 7. DIN Rail Mounting
–
Step 2
3.
Turn
OFF
the customer-supplied 24V DC supply prior to connecting to unit.
4.
Wire the 24V DC supply to supplied power plug. The chassis must be grounded.
5.
Insert the power plug PN 43541 into the DC power receptacle (Figure 8)
6.
Install the interlock plug, PN 43536 (Figure 9).
7.
Configure the interlock plug by removing the pre-inserted jumpers that are not
required based on the Interlocks section of this user guide. Connect the desired
interlock switches as needed.