6 Error Messages
Any operational error is indicated by the red LED blinking and accompanied by an alarm buzz.
Furthermore, the display indicates an error status message. To stop the alarm buzz, the status
message should be removed from the display. Return to the starting menu by pressing
STOP
.
If abnormal operating conditions occur during the battery charging, the following error messages
will appear on the display.
6.1 Error message "VS Polarity"
This message is displayed in case the current cables are connected properly but the voltage sense
cables are connected in opposite polarity either on the side of a device or the side of a battery.
Figure 6-1: Error message "VS Polarity"
6.2 Error message "Polarity"
This message is displayed in case the current cables are connected in opposite polarity either on
the side of a device or the side of a battery.
Figure 6-2: Error message "Polarity"
In this case connect the current cables correctly and repeat the charging process.
6.3 Error message "Overcurrent"
This message is displayed if the charge current is higher than the set or maximum permissible
current values.
Figure 6-3: Error message "Overcurrent"