Choosing the Right Power Cord
Long or thin cords can drain the power provided to an electrical device by the generator. When
using such cords, allow for a slightly higher rated wattage requirement for the electrical device. See
the table below for recommended cords based on the power requirement of the electrical device.
DEVICE REQUIREMENTS
WIRE GAUGE BY LENGTH (ft.)
AMPS
WATTS (120/240V)
10
25
50
100
150
5
600/1200
18
16
14
12
10
10
1200/2400
16
14
12
12
10
15
1800/3600
14
14
12
12
10
20
2400/4800
12
12
12
10
10
25
3000/6000
12
10
10
10
8
30
3600/7200
10
10
10
8
NR
40
4800/9600
8
8
6
6
NR
50
6000/12000
6
6
6
NR
NR
*NR = NOT RECOMMENDED *Gauge based on twisted copper wire