background image

7

 

S

UBMITTAL

 

R

ECORD

 

FOR

 

D

URA

S

TACK

 

M

ODELS

 

DCL,

 

DAS1,

 

DIS1,

 

DIS2

 

AND

 

DIS4

 

M&G

 

D

URA

V

ENT

 

|

 

10

 

J

UPITER

 

L

ANE

 

|

 

A

LBANY

,

 

N

EW

 

Y

ORK

 

www.duravent.com

 

 

SECTION D-COMPONENTS

 

 

HIGH PRESSURE SYSTEM – up to 60” WC 

THERMAL EXPANSION JOINT and ODD LENGTH  

For Thermal Expansion we recommend using a Bellow Length (LB). 
For ODD Length we recommend using a Variable Length (LV).

 

 

LOW PRESSURE SYSTEM – up to 6” WC 

THERMAL EXPANSION and ODD LENGTH  

For thermal Expansion and ODD Length we recommend using 
an Adjustable Length (LA). 
 

THERMAL EXPANSION

 

 

The inner pipe  of Model DAS-PRO and DIS-PRO is load bearing and its thermal 
expansion is the same as that  of a continuous  pipe. A simplified  rule for  exhaust 
pipe expansion estimation is that  the axial growth will be approx. 1” per 100’ of 
pipe length for each 100°F the flue gas temperature is above the surrounding air 
temperature. 

See Thermal Expansion Formula on page 3.

 

 

When assembled in any orientation,  the  amount of thermal  expansion of the  inner 
pipe is directly dependent on the inner wall temperature and the length of pipe 
between fixed points.  Good installation  practice  requires  that  expansion  greater 
than  1/4 inch will be  compensated for using a Bellows Joint or Adjustable Length, 
depending on the maximum pressure encountered. 

The flanged inner piping joints have negligible flexing capacity, and in addition, tees 
and elbows  are  not  designed to withstand  bending  moment  forces. Because the 
amount of outer  casing  axial  movement is the same as inner casing movement, the 
outer jackets of piping must slide to avoid excessive forces on Tees, Elbows of fixed 
points.  To accommodate outer casing movements, external guides along walls at 
floors or in lateral breechings must allow for movement of pipe.

 

 

BELLOWS LENGTH

 

 

For exhaust pressure to 60 inches  of water column, Bellows are recommended 
for expansion and vibrational movements of the piping.

 

 

The Bellows has a 0.035” thick or heavier straight stainless steel liner to 
protect  the thinner spring material from  heat and flow  effects. It is used anywhere in 
a system for axial and vibrational  movements  only and must  be accurately 
supported and guided. This part has limited  lateral movement (1/8”  max.) and 
lateral offsets and parallel misalignments should be eliminated. The purpose of the 
liner is to minimize  contact, smooth flow, control erosion and eliminate resonance 
caused by exhaust gases passing through the bellows.  

See Table 7 for Bellows 

Properties 

 

Typical Bellow design 

 

 

 

 

ADJUSTABLE LENGTH (LA) - EXPANSION JOINT

 

 

The 

LA 

has two functions. It is used to compensate for thermal expansion and 

make up odd lengths of vent.. 
 
It is shipped with  graphite band assembly preassembled on the sliding inner pipe.

 

The 

LA

 is adjustable from 7 1/4 to 28 3/8 inch.  

See Figure 15

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure

 

15

 

 

Adjustable

 

Length

 

(LA)

 

 
 

 

 
 
 
 
 
 
 
 
 

Gas

 

Flow

 

Cuttable

 

half

 

siding

  

outer

 

casing

 

Moveable

 

gasket

 

assembly

 

Cuttable

 

sliding

 

inner

 

wall

 

Spacing

 

Tool

 

supplied

 

Wrench

 

 

by

 

others

 

Summary of Contents for DAS1 22 E30 CE

Page 1: ...INSULATED DIS1 1 INCH CERAMIC FIBER INSULATED DIS2 2 INCH CERAMIC FIBER INSULATED DIS4 4 INCH CERAMIC FIBER INSULATED DCL SINGLE WALL MATERIAL SELECTION FLUE INNER WALL CASING OUTER WALL 304 304 316...

Page 2: ...tent service at temperatures not exceeding 1800 F As such Model DAS PRO and D I S PRO Models are suitable for use with ovens and furnaces as described in the Chimney Selection Chart of NFPA No 211 in...

Page 3: ...d ceiling or floor above the hood through any concealed spaces to or through the roof to maintain the integrity of the fire separations required by the applicable building code provisions If the build...

Page 4: ...re used to anchor a chimney against upward downward and angular displacement 2 These supports and guides used with thermal expansion devices prevent bending stresses on the chimney elbows and joints 3...

Page 5: ...23 19 16 12 14 to 24 19 19 16 14 10 26 to 36 15 15 13 11 8 Dimensions are in inches diameter and feet distance EXTERIOR CORROSION PROTECTION It is recommended to apply an exterior grade high heat pain...

Page 6: ...F S 2000 is water soluble and should not be used where exposed to weather Part No S 375 Nuflex 302 General Purpose is a low temperature grey silicone 450 F only for weathering sealing on outdoor seams...

Page 7: ...band when assembled Figure 10 Joint Assembly Step 5 STEP 6 Secure the Outer Casing Band with the Outer Band BSE Joint installation is now completed NOTE For exterior installations it is recommended t...

Page 8: ...not designed to withstand bending moment forces Because the amount of outer casing axial movement is the same as inner casing movement the outer jackets of piping must slide to avoid excessive forces...

Page 9: ...IGHT LIMITS section Figure 17 T90 TEE PRECAUTION 1 Use an adjustable length in all horizontal breechings or laterals 2 If more than of thermal expansion is expected between the tee and the next fixed...

Page 10: ...ly as described in JOINT ASSEMBLY section Elbows are used in combination to make different angles ranging from 3 to 90 in horizontal and vertical segments of the duct system ELBOW 3 degree E3 Figure 2...

Page 11: ...8 11 7 8 32 1 4 26 3 8 2 5 8 6 7 8 12 1 2 34 1 4 28 3 8 2 3 4 7 1 8 13 36 1 4 30 3 8 2 3 4 7 3 8 13 5 8 38 1 4 32 3 8 2 7 8 7 5 8 14 1 8 40 1 4 34 3 8 3 8 14 3 4 42 1 4 36 3 8 3 8 1 4 15 3 8 44 1 4 D...

Page 12: ...ow DIS4 Diameter in 3 15 30 45 90 5 1 2 2 3 4 6 1 8 10 24 1 2 6 1 2 2 3 4 6 1 4 10 1 4 25 1 2 7 1 2 2 3 4 6 3 8 10 1 2 26 1 2 8 1 2 2 3 4 6 1 2 10 7 8 27 1 2 9 1 2 2 7 8 6 5 8 11 1 8 28 1 2 10 1 2 2 7...

Page 13: ...imum support the entire perimeter of the Plate Support must be attached to structural framing WARNING RISK OF FIRE DO NOT ATTACH THE PLATE SUPPORT TO COMBUSTIBLE CONSTRUCTION HEAVY DUTY WALL SUPPORT W...

Page 14: ...D HEAVY DUTY FLOOR GUIDE FGHD A Heavy Duty Floor Guide is similar in function to a Heavy Duty Wall Guide or Full Angle Ring but has been modified for use at floor penetrations The angle brackets and s...

Page 15: ...ration It can be supported by bracing with a Half Angle Ring HAR an Anchor Plate AP or an Anchor Plate Length APL SECTION F ROOF PENETRATION and FLASHINGS Flashing F The flat Roof Flashing F is used i...

Page 16: ...xhaust system backfire Engines have the potential to inject unburned fuel into an exhaust system during start up or due to an engine malfunction This unburned fuel creates a condition where a backfire...

Reviews: