10.7. D-LX 100 … /96 Ex for Hazardous Areas Class I, Div. 2, Group A,B,C&D
R1
1 /
4"
SW 4
6
WAF
4
6
80
92
90
152
24
3 mm
22
Purge air connection G 1/2"
Scanning tube connection G 1¼"
Viewing angle 6°
(D-LX 100 UL vert. 12°)
Cover
Set screw
(Fig. 10)
Dimensional drawing: D-LX 100…/96Ex
!
Explosion
Hazard!
This flame scanner is suitable for use in Class I, Division 2, Groups A, B, C & D or non-
hazardous areas only.
Exposures to some chemicals may degrade the sealing properties of used in the relays
of the flame scanner. It is recommended that the sealing of the relays are checked
periodically for any degradation of properties. In case of any degradation the flame
scanner should be send to the manufacturer for service.
Before opening the housing in any hazardous location (e.g. explosive atmosphere), the
flame scanner must be disconnected from its power source.
Area classification:......................................... Class I, Division 2, Group A, B, C & D
Viewing pipe connection: .............................. G 1 ¼” pipe thread
Purge air connection: .................................... G ½” pipe thread
Weight:........................................................... 1.8 kg (3.96 lbs.)
Cable entry: ................................................... ½” NPT (F) for conduit connection
Wiring according to figure 7