D-LX 100
Page
13
10. Technical Data
•
Permissible ambient temperatures: -20°C…+60°C (0
°
F…+140
°
F,
(other temperatures upon request)
•
Safety
time:.....................................1
s (other times available upon request)
•
Permissible operating modes:........intermittent and continuous operation; 72-hour operation in
systems operating according to TRD 604
•
Enclosure rating (EN 60529):.........IP67 (rating not associated with FM logo mark)
•
Sighting tube connection:...............G1¼”
•
Purge air connection: .....................G½”
•
Electrical connection: ...................1.5m (5 ft.) cable (8 conductor, 1 mm² / 18 gauge),
T = -60 to +180°C (-80
°
F to 360
°
F)
•
Weight: ...........................................approx. 1.8 kg (4 lb.)
10.1. Technical Data of the Integrated Flame Scanner
•
Optical angle of view ......................6°; for the D-LX 100 UL: 6
°
horiz., 12
°
vert.
•
Spectral
sensitivity..........................185 nm – 260 nm
D-LX 100 UL
190 nm - 520 nm
D-LX 100 UA
280 nm - 410 nm
D-LX 100 UAF
300 nm - 1100 nm
D-LX 100 IS
780 nm - 1800 nm
D-LX 100 IG
•
Flame scanner amplification: .........2 levels: standard V2= V1x3, (not D-LX 100 UL)
10.2. Technical Data and Configuration of Inputs and Outputs
•
Connection to power supply...........L+, L-, PE / grounded lead
•
Power
supply:.................................24 VDC
±
20%, approx. 5 W
•
Fuse
protection:..............................F1= 0.315 A, semi-slow, MST 250
•
Current output 0 / 4 - 20 mA ..........Flame intensity / 150 Ohm maximum load
•
Flame
contact.................................Closer; active if flame is present
•
Fault
contact...................................Closer; active if no fault is present
Series connection with the flame contact as possible
second
shut-off
path
.
•
Switching capacity of the relay contacts / fuse F2, slow, MST250:
min:.................................................10 VAC/dc, 10 mA
max:................................................250
VAC,
2.0 A / cos
ϕ
=1,0 (resistive load), F2= 2A slow
1.0 A / cos
ϕ
=0,4 (inductive load), F2= 1A slow
0.2 A / cos
ϕ
=0,2 (inductive load), F2=0.2A slow
24 VDC,
0.5 A with spark extinc.
F2=0.5A slow
110 VDC,
0.2 A with spark extinc.
F2=0.2A slow
220 VDC,
0.1 A with spark extinc.
F2=0.1A slow
The flame scanner is constructed such that there is potential separation between the power
supply (24 VDC) and the unit’s internal voltage (UB = 20 VDC / 5 VDC). The current output is
galvanically connected to the internal voltage.
The relay contact for the flame ON signal is delivered with a fuse, F2 = 0.5 A, slow, MST250, for
24 VDC voltage switches. If connecting other switch voltages, this fuse must be exchanged
accordingly.