7.2. Flame Recognition Thresholds as a Function of the Rocker Switch Setting
Rocker Switch
Setting
Beginning of
Range 0/4 mA
Shut-off
Threshold 5/8 mA
Switch-On
Threshold 5/8 mA
End of Range
20 mA
0 2048
2560 2816
4095
1 1536
1984 2208
3328
2 1024
1431 1634
2650
3 768
1088
1248
2048
4 608 894 1036
1750
5 384 626 746
1350
6 256 448 544
1024
7 128 288 368 768
8 *
64
132
166
336
9 32 56 68
128
• The flame recognition threshold is set to position
8
when delivered from the factory
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0
1
2
3
4
5
6
7
8
9
UG
11
0
-02-
00
1
Rocker Switch Setting
Pul
se fr
equ
ency
Beginning of Range 0 / 4 mA
Shut-Off Threshold 5 / 8 mA
Switch-On Threshold5 / 8 mA
End of Range 20mA
(Fig. 4)
Flame recognition thresholds as function of the rocker switch setting