9.3. Selection Criteria for the D-LX 100 All-In-One Flame Scanner
Model
Spectral
Suitable for Following Fuels
Characteristics
Range [nm]
Gas
Oil
Coal
Wood
D-LX 100 UL
185 – 260
++ +
Monitoring of gas and oil flames
D-LX 100 UA
190 - 520
++ ++
{
Monitoring of gas and oil flames; also for low-NO
x
combustion.
D-LX 100 UAF
280 - 410
+ ++
Monitoring of very intense gas and oil flames; also for low-
NO
x
combustion.
D-LX 100 IS
300 - 1100
++ + +
Monitoring of oil burners, even if additional fuels are also
combusted.
D-LX 100 IG
780 - 1800
{
+ ++ ++
Monitoring of oil and wood flames, as well as coal flames.
Explanation of symbols:
++
Flame scanner is
ideally suited
for this fuel.
+
Flame scanner is
well suited
for this fuel.
{
Flame scanner is
conditionally suited
for this fuel. The monitoring characteristics depend for the most part on the
combustion
technique.
!
Due to local regulations the flame sensor might not be approved for monitoring of gas flames.
This information is based on years of experience in a great proportion of combustion systems. Variations due to differing flame
behaviour, caused by special combustion techniques cannot be taken into account or excluded. Therefore, deviations from table
are possible.
9.4. Overview of D-LX 100 All-In-One Flame Scanner
Axial Plug Connection
Flameproof housing
II 2G EEx de IIC T6
Flameproof housing
Class I, Division 1
Group B,C&D
Version for
Class I, Division 2
Group A,B,C&D
Version for
II 3G EEx nC IIC T6
D-LX 100 UL-P
D-LX 100 UL/94Ex
D-LX 100 UL/95Ex
D-LX 100 UL/96Ex
D-LX 100 UL/97Ex
D-LX 100 UA-P
D-LX 100 UA/94Ex
D-LX 100 UA/95Ex
D-LX 100 UA/96Ex
D-LX 100 UA/97Ex
D-LX 100 UAF-P
D-LX 100 UAF/94Ex
D-LX 100 UAF/95Ex
D-LX 100 UAF/96Ex
D-LX 100 UAF/97Ex
D-LX 100 IG-P
D-LX 100 IG/94Ex
D-LX 100 IG/95Ex
D-LX 100 IG/96Ex
D-LX 100 IG/97Ex
D-LX 100 IS-P
D-LX 100 IS/94Ex
D-LX 100 IS/95Ex
D-LX 100 IS/96Ex
D-LX 100 IS/97Ex
9.5. Options
The D-LX 100 All-In-One Flame Scanner is normally delivered with the options listed in the table
below. Should other options be required, please make them known when ordering.
“Flame intensity” current output
0 - 20 mA
4 - 20 mA
Safety time
1 s
3 s
5 s
Note:
the options shown in the shaded areas are standard; please indicate when placing an order