Dunkirk PVWB Installation Instructions Manual Download Page 7

7

CHECK YOUR CHIMNEY

This is a very important part of your heating system. It must be
clean, the right size, properly constructed and in GOOD
CONDITION. No boiler can function properly with a bad
chimney. Fig. 7 gives typical chimney sizes. Fig. 8 gives you
an idea how a boiler might be vented to a chimney. Note that
the height (HT) is measured from the vent pipe to the top.

CHIMNEY SIZING

Chimney sizing, and all other aspects of the vent installation
must be in accordance with Part 7 of the National Fuel Gas
Code, ANSI Z223.1 latest revision, and applicable provisions
of the local building codes.
In Canada, follow CAN/CGA B149.1 and B149.2, Installation
Codes for Gas Burning Appliances and Equipment.

CONNECTING THE VENT DAMPER AND VENT
CONNECTOR

Refer to Fig. 1 flue diagram for the size and location of the vent
(flue opening). Use a 28 gauge (minimum) galvanized pipe to
connect to the chimney.

IMPORTANT - 

The

 

damper blade on the furnished vent damper

has a 1/2 square inch hole (approximately3/4 diameter). On
boilers equipped with standing pilot, the hole must be left open.
On boilers equipped with intermittent ignition, the hole should
be plugged by using the plug supplied with the vent damper.

1. Position furnished vent damper on top of flue outlet collar.

Fasten damper securely to flue outlet collar with sheet
metal screws. Make sure damper blade has clearance to
operate inside of diverter.
On 2 section boilers equipped with vent damper, the
supplied 4-inch vent damper is equipped with a 3- to 4-
inch adapter so that the 4-inch vent damper may be
installed on the boiler’s 3-inch flue outlet collar. Fasten all
fittings securely.

As An Option (U.S.A. Only)

The damper may be installed in any horizontal or vertical
position, closer to the flue outlet collar preferred. Follow
the diagrams - Figures 9, 10 and 11.

2. Install the vent damper to service only the single boiler for

which it is intended. The damper position indicator shall
be in a visible location following installation. Locate the
damper so that it is accessible for servicing.

3. The damper must be in the open position when appliance

main burners are operating.

4. The boiler is equipped with a factory wired harness that

plugs into the vent damper.

5. Vent pipe must be same size as the flue outlet collar, except

2 section boilers with vent damper as noted above.

6. Slope pipe up from boiler to chimney not less than 1/4” per foot.

Chimney and Vent Pipe Connection

For boilers for connection to gas vents or chimneys, vent installations shall be in

accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI

Z223.1-latest revision and applicable provisions of the local building codes.

7. Run pipe as directly as possible with as few elbows as

possible.

8. Do not connect to fireplace flue.
9. End of vent pipe must be flush with inside face of chimney

flue. Use a sealed-in thimble for the chimney connection.

10. Horizontal run should not be longer than 

3

/4 the

chimney height (HT) (Fig, 8).

The sections of vent pipe should be fastened with sheet metal
screws to make the piping rigid. Horizontal portions of the vent
system must be supported to prevent sagging. Use stovepipe
wires every 5' to support the pipe from above If the vent pipe
must go through a crawl space, double wall vent pipe should
be used Where vent pipe passes through a combustible wall
or partition, use a ventilated metal thimble. The thimble should
be 4 inches larger in diameter than the vent pipe.

Boiler Input

*HT.

*HT.

*HT.

Btuh

10-15 Ft.

10-25 Ft.

25 Ft. UP

Up to 100,000

6 x 6

6 x 5

5 x 5

Up to 155,000

6 x 7

6 x 6

6 x 5

Up to 230,000

7 x 8

7 x 7

6 x 7

Up to 350,000

9 x 9

8 x 9

8 x 8

FLUE AREA IN INCHES

* HT = top of thimble to top of flue. See Fig. 8

For boiler input refer to table, page 2.
For information only - not meant to imply minimum sizes.

MINIMUM VENT PIPE CLEARANCE

Wood and other combustible materials must not be closer than
6" from any surface of single wall metal vent pipe. Listed Type
B vent pipe or other listed venting systems shall be installed in
accordance with their listing.

REMOVING EXISTING BOILER FROM
COMMON VENTING SYSTEM

When an existing boiler is removed from a common venting
system, the common venting system is likely to be too large
for proper venting of the appliances remaining connected to it.

At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected to
the common venting system placed in operation, while the other
appliances remaining connected to the common venting system
are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and

horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.

FIG. 7 - TYPICAL CHIMNEY SIZES

Summary of Contents for PVWB

Page 1: ...t W Hot W Hot Wa a a a ater ter ter ter ter Boiler Boiler Boiler Boiler Boilers s s s s These Gas Fired Water Boilers are low pressure sectional cast iron boilers Designed Certified by C S A Canadian...

Page 2: ...WB 9D 9 280 226 197 7 30 BASIC BOILER UNIT NO DIMENSIONS Inches NATURAL AND PROPANE GAS GAS FIRED HOT WATER BOILERS MBH 1 000 Btuh British Thermal Unit Per Hour Boilers are equipped for altitudes up t...

Page 3: ...with the correct conversion information Check to be sure you have the right size boiler before starting the installation _ See rating and capacity table on previous page Also be sure the new boiler is...

Page 4: ...installed in the room Consult section 6 3 1 of the National Fuel Gas Code for further information including approved methods for reducing clearances in large rooms 5 Equipment shall be installed in a...

Page 5: ...hin 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure shall be provided The openings shall communicate directly or by the ducts with the outdoors or spaces crawl...

Page 6: ...at the pump A hot water boiler installed above radiation level must be equipped with a low water cutoff device A periodic inspection is necessary as is flushing of float type devices per manufacturer...

Page 7: ...s noted above 6 Slopepipeupfromboilertochimneynotlessthan1 4 perfoot Chimney and Vent Pipe Connection For boilers for connection to gas vents or chimneys vent installations shall be in accordance with...

Page 8: ...from a cigarette cigar or pipe 6 After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above return doorswindows ex...

Page 9: ...product carrying areas of the appliance must be checked annually by you with particular attention given to deterioration from corrosion or other sources If you see corrosion or other deterioration con...

Page 10: ...d suitable for LP gas on male threads only 3 Use ground joint unions 4 Install a sediment trap upstream of gas controls 5 Use two pipe wrenches when making the connection to the gas valve to keep it f...

Page 11: ...ffect on the operation of your boiler system BE SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT Locate the thermostat about five feet above the floor on an inside wall It may be mounted...

Page 12: ...S SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC WIRE OR ITS EQUIVALENT NOTE THE CIRCULATOR HARNESS IS FACTORY WIRED TO THE AQUASTAT THIS HARNESS NEEDS...

Page 13: ...THE ORIGINAL WIRE AS SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC WIRE OR ITS EQUIVALENT NOTE THE CIRCULATOR HARNESS IS FACTORY WIRED TO THE AQUASTAT...

Page 14: ...heated its pressure increases It expands into the EX TROL tank compressing the air in the tank This compressed air cushion permits the water in the system to expand as the temperature changes The diap...

Page 15: ...Boiler HOW A HOT WATER SYSTEM OPERATES Your entire heating system boiler piping and radiation units is filled with water As the water in the boiler is heated it is pumped from the top of the boiler t...

Page 16: ...fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system an...

Page 17: ...se to OFF Do not force Operating Your Boiler AUTOMATIC GAS VALVE The Automatic Gas Valve opens or closes according to the heat requirements of the thermostat and temperature limit control It closes if...

Page 18: ...gure 17 ADJUST LIMIT CONTROLS Instructions for each control are included with the controls These settings can be changed after you have had some idea how the system works Example If your system does n...

Page 19: ...ating conditions with the burners properly adjusted it should not be necessary to clean the boiler flue gas passages However to assure trouble free operation we recommend that you have the flue passag...

Page 20: ...power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in closed posi...

Page 21: ...5 45 900 425 45 900 10 Knob Service Door Pair 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 11 Jacket Service Door 425 00 912 425 00 913 425 00 914 425 00 915...

Page 22: ...5 532 146 15 532 146 15 532 6A Main Burner with Pilot Bracket 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 Pilot Burner Nat 146 62 095 146 62 092 146 62 092...

Page 23: ...Taco 007 Circulator CI 001 03 10 1 x 2 Nipple 146 07 044 11 1 Bent Return Nipple 146 07 003 12 Intermittent Pilot Control 146 62 070 Spill Switch 36TX16 6281 340 F 146 60 002 Rollout Switch 146 29 002...

Page 24: ...14683002 Rev 3 November 2004...

Reviews: