Before You Start
Installers - Follow local regulations with respect to
installation of CO detectors. Follow maintenance
recommendations in this instruction manual.
T e c h n i c i e n s - V e u i l l e z v o u s c o n f o r m e r a la
réglementation en vigueur concernant I’ installation des
d
é
tecteurs d’oxyde de carbone. Suivre les consignes
d’entretien figurant dans le manuel d
í
nstruction ci-joint.
KEEP BOILER AREA CLEAN AND FREE FROM COMBUSTIBLE MATERIALS,
GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS
Gas Code
(NFPA54/ANSI Z223.1-latest edition), or the
manufacturer for correct orifice sizing information. High
altitude orifices are available from the boiler manufacturer.
Canada Only
-
For altitudes in the range of 2,000-4,500
feet above sea level, boilers may be field equipped for use
at high altitude by using a certified field conversion kit. The
change in main burner orifice size results in the boiler’s
input rating being reduced by 10%. The conversion shall
b e c a r r i e d o u t b y a m a n u f a c t u r e r ’ s a u t h o r i z e d
representative, in accordance with the requirements of the
manufacturer, provincial or territorial authorities having
jurisdiction and in accordance with the requirements of the
CSA-B149.1 and CSA-B149.2 Installation Codes. The
certified field conversion kit includes a conversion data
plate, which must be attached to the boiler adjacent to the
rating plate, indicating that the boiler has been converted
for high altitude use. The conversion data plate must be
filled in with the correct conversion information.
Check to be sure you have the right size boiler before starting
the installation. _ See rating and capacity table on previous
page. Also be sure the new boiler is or the type of gas you are
using. Check the rating plate on the right side of the boiler.
You must see that the boiler is supplied with the correct type
of gas, fresh air for combustion, and a suitable electrical supply.
Also, the boiler must be connected to a suitable venting system
and an adequate piping system. Finally, a thermostat, properly
located, is needed for control of the heating system. If you
have any doubts as to the various requirements, check with
local authorities and obtain professional help where needed.
Take the time to complete all of the steps for SAFE and
PROPER operation of the heating system.
If this boiler is installed in a building under construction,
special care must be taken to insure a clean combustion
air supply during the construction process. Airborne
particulates such as from drywall dust and from fiberglass
insulation can clog the burner ports and cause incomplete
combustion and sooting.
Where required by the authority having jurisdiction, the
installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No. CSD-1.
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI Z223.1-
latest revision.
In Canada, the boiler shall be installed according to CSA-
13149.1 and .2, Installation Code for Gas Burning
Appliances and Equipment.
Summary of Contents for PVWB