Dunkirk PVWB Installation Instructions Manual Download Page 19

19

Maintaining Your Boiler

BURNERS

A visual check of the pilot end main burner flames should be
made at least once each year, preferably at the beginning of
the heating season. See page 21

RELIEF VALVE

This valve should open automatically if the system pressure
exceeds the pressure rating (usually 30 psi) of the relief valve.
Should it ever fail to open under this condition, shut down your
system. Drain the system until system pressure is reduced
below the relief valve pressure rating. If valve discharge oc-
curs, or if valve fails to open as described above, contact an
authorized contractor or qualified service technician to replace
the relief valve and inspect the heating system to determine
the cause, as this may indicate an equipment malfunction.
This valve should be tested every month during periods of boiler
operation, and at the beginning and end of any extended non-
service period. Prior to testing, make certain discharge pipe is
properly connected to valve outlet and arranged so as to con-
tain and safely dispose of boiler discharge. Test at normal sys-
tem operating pressure. Hold the trip lever fully open for at
least five seconds in order to flush free any sediment that may
lodge on the valve seat. Then permit the valve to snap shut.

EXPANSION TANK

As previously noted, this tank may become waterlogged, or
may receive an excess of air. Frequent automatic opening of
the relief valve indicates water logging. A high boiler tempera-
ture accompanied by unusually low radiation unit temperature
(and “knocking”) indicates excess air in tank.
To correct either condition, close the valve between the boiler
and the tank. Drain the tank until it is empty. Check all the tank
plugs and fittings. Tighten as necessary. Open the valve be-
tween the boiler and tank. Water will rise to the normal height
in the tank if you have an automatic fill valve (otherwise, manu-
ally refill the system).

BOILER FLUE PASSAGES

Under normal operating conditions, with the burners properly
adjusted, it should not be necessary to clean the boiler flue
gas passages. However, to assure trouble-free operation, we

recommend that you have the flue passages, burner
adjustment, and operation of the controls checked once each
year by a competent Service Technician.

Before the start of each season

 (or whenever system has

been shut down for some time) recheck the whole system for
leaks ... and recheck the boiler and vent pipe for leaks. Replace
or patch any boiler seals that are faulty.

VENT PIPE

The venting of this unit is very important and the piping
should be checked at least once a season. If the vent piping
shows any sign of leaking, replace it immediately.

WATER SYSTEM

If system is to remain out of service during freezing weather,
always 

drain it 

completely (water left in to freeze will crack the

pipes and/or boiler).

CLEANING YOUR BOILER AND BURNERS

Flue passages between sections should be examined yearly
and cleaned if necessary. To clean, remove burners, pilot, and
vent pipe, Remove top and front jacket panels. Remove the
two screws attaching the intermediate front panel to the left
and right side jacket panels. Remove the draft diverter and
intermediate front panel as a unit. Carefully remove the cerafelt
gasket strips. Clean passageways between sections with a
flexible handle wire brush. Remove dirt from bottom of boiler
and from between sections by vacuuming. Make sure all flame
ports in burners are open and clear. Shake out or blow out all
loose dirt in burners. Reseal seams between adjacent sections
as necessary with 400

°

 F RTV silicone sealant. Reassemble

all parts. Be sure to check tightness of pilot connections and
condition of burner flames after reassembly (see Figures 17
and 18). Be sure vent pipe connections to chimney are secure
and no obstructions are present.

CIRCULATOR PUMP ISOLATION VALVES

The isolation valves in the circulator pump flanges should be
operated manually once or twice per year to prevent the valves
from becoming stuck in the open position Rotate the valves
from the open position to the closed position and back to the
open position.

Summary of Contents for PVWB

Page 1: ...t W Hot W Hot Wa a a a ater ter ter ter ter Boiler Boiler Boiler Boiler Boilers s s s s These Gas Fired Water Boilers are low pressure sectional cast iron boilers Designed Certified by C S A Canadian...

Page 2: ...WB 9D 9 280 226 197 7 30 BASIC BOILER UNIT NO DIMENSIONS Inches NATURAL AND PROPANE GAS GAS FIRED HOT WATER BOILERS MBH 1 000 Btuh British Thermal Unit Per Hour Boilers are equipped for altitudes up t...

Page 3: ...with the correct conversion information Check to be sure you have the right size boiler before starting the installation _ See rating and capacity table on previous page Also be sure the new boiler is...

Page 4: ...installed in the room Consult section 6 3 1 of the National Fuel Gas Code for further information including approved methods for reducing clearances in large rooms 5 Equipment shall be installed in a...

Page 5: ...hin 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure shall be provided The openings shall communicate directly or by the ducts with the outdoors or spaces crawl...

Page 6: ...at the pump A hot water boiler installed above radiation level must be equipped with a low water cutoff device A periodic inspection is necessary as is flushing of float type devices per manufacturer...

Page 7: ...s noted above 6 Slopepipeupfromboilertochimneynotlessthan1 4 perfoot Chimney and Vent Pipe Connection For boilers for connection to gas vents or chimneys vent installations shall be in accordance with...

Page 8: ...from a cigarette cigar or pipe 6 After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above return doorswindows ex...

Page 9: ...product carrying areas of the appliance must be checked annually by you with particular attention given to deterioration from corrosion or other sources If you see corrosion or other deterioration con...

Page 10: ...d suitable for LP gas on male threads only 3 Use ground joint unions 4 Install a sediment trap upstream of gas controls 5 Use two pipe wrenches when making the connection to the gas valve to keep it f...

Page 11: ...ffect on the operation of your boiler system BE SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT Locate the thermostat about five feet above the floor on an inside wall It may be mounted...

Page 12: ...S SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC WIRE OR ITS EQUIVALENT NOTE THE CIRCULATOR HARNESS IS FACTORY WIRED TO THE AQUASTAT THIS HARNESS NEEDS...

Page 13: ...THE ORIGINAL WIRE AS SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC WIRE OR ITS EQUIVALENT NOTE THE CIRCULATOR HARNESS IS FACTORY WIRED TO THE AQUASTAT...

Page 14: ...heated its pressure increases It expands into the EX TROL tank compressing the air in the tank This compressed air cushion permits the water in the system to expand as the temperature changes The diap...

Page 15: ...Boiler HOW A HOT WATER SYSTEM OPERATES Your entire heating system boiler piping and radiation units is filled with water As the water in the boiler is heated it is pumped from the top of the boiler t...

Page 16: ...fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system an...

Page 17: ...se to OFF Do not force Operating Your Boiler AUTOMATIC GAS VALVE The Automatic Gas Valve opens or closes according to the heat requirements of the thermostat and temperature limit control It closes if...

Page 18: ...gure 17 ADJUST LIMIT CONTROLS Instructions for each control are included with the controls These settings can be changed after you have had some idea how the system works Example If your system does n...

Page 19: ...ating conditions with the burners properly adjusted it should not be necessary to clean the boiler flue gas passages However to assure trouble free operation we recommend that you have the flue passag...

Page 20: ...power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in closed posi...

Page 21: ...5 45 900 425 45 900 10 Knob Service Door Pair 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 11 Jacket Service Door 425 00 912 425 00 913 425 00 914 425 00 915...

Page 22: ...5 532 146 15 532 146 15 532 6A Main Burner with Pilot Bracket 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 Pilot Burner Nat 146 62 095 146 62 092 146 62 092...

Page 23: ...Taco 007 Circulator CI 001 03 10 1 x 2 Nipple 146 07 044 11 1 Bent Return Nipple 146 07 003 12 Intermittent Pilot Control 146 62 070 Spill Switch 36TX16 6281 340 F 146 60 002 Rollout Switch 146 29 002...

Page 24: ...14683002 Rev 3 November 2004...

Reviews: