![Dunkirk PVWB Installation Instructions Manual Download Page 2](http://html1.mh-extra.com/html/dunkirk/pvwb/pvwb_installation-instructions-manual_2539845002.webp)
2
New York City MEA Number 39-86-E Vol. IV.
The Ratings marked “Net 1=B=R Ratings” indicate the amount
of remaining heat input that can be used to heat the radiation
or terminal units. The Net 1=B=R Ratings shown are based on
an allowance of 1.15 in accordance with the factors shown on
the 1=B=R Standard as published by The Hydronics Institute.
Selection of boiler size should be based upon “Net 1=B=R
Rating” being equal to or greater than the calculated heat loss
of the building.
The manufacturer should be consulte
d before
selecting a boiler
for installations having unusual piping and pickup requirements.
These boilers must stand on a non-combustible floor. If in
Boiler Ratings and Capacities
Electronic Ignition Continuous Pilot
NO. OF
AGA/CGA
HEATING NET I=B=R
With
With
SECTIONS
INPUT
CAPACITY
RATING
FLUE
"A"
Vent Damper
Vent Damper
*MBH
*MBH
*MBH
DIAMETER WIDTH
PWB-2D
PVWB-2D
2
37.5
30
26
4‡
8
PWB-3D
PVWB-3D
3
70
57
50
5
11¼
PWB-4D
PVWB-4D
4
105
85
74
6
14½
PWB-5D
PVWB-5D
5
140
113
98
6
17¾
PWB-6D
PVWB-6D
6
175
142
123
7
21
PWB-7D
PVWB-7D
7
210
170
148
7
24¼
PWB-8D
PVWB-8D
8
245
198
172
7
27½
PWB-9D
PVWB-9D
9
280
226
197
7
30¾
BASIC BOILER UNIT NO.
DIMENSIONS
(Inches)
NATURAL AND PROPANE GAS
GAS-FIRED HOT WATER BOILERS
* MBH = 1,000 Btuh = British Thermal Unit Per Hour
Boilers are equipped for altitudes up to 2,000 feet only
U.S.A. Only - For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level.
Canada Only - Boilers may be used at high altitude by using a certified field conversion kit, resulting in a 10% derate.
+ Heating Capacity based on D.O.E. (Department of Energy) test procedure. Add 5½” to height when vent damper is used.
‡ 2 section boilers are equipped with a 3” diameter flue collar on the draft diverter, and use a furnished 3” x 4” increaser fitting to install
the furnished 4” vent damper.
stalled on a combustible floor, use Combustible Floor Base
Number 42135-1 or 146-14-031 (2-6 section boilers) or
42135-2 or 146-14-032 (7-9 section boilers).
BOILERS FOR USE AT HIGH ALTITUDE
This boiler is factory equipped for use at altitudes of 0-2,000
feet above sea level. For use at altitudes above 2,000 feet
above sea level, the input ratings are reduced by a change in
main burner orifice size.
U.S.A. Only
-
For altitudes above 2,000 feet above sea
level, input ratings should be reduced at the rate of 4% for
each 1,000 feet above sea level. Consult the
National
Fuel
FIG. 1
Summary of Contents for PVWB
Page 24: ...14683002 Rev 3 November 2004...