Dunkirk PVWB Installation Instructions Manual Download Page 14

14

Equipment and Optional Accessories - What They Do

RELIEF VALVE

You must have a relief valve on your boiler. Water expands as
it is heated. If there is no place for the water to expand into,
water pressure will build up inside the boiler and system. Should
this happen, the relief valve will automatically open at a
predetermined pressure. This will relieve the strain on the boiler
and system. Run a pipe from the relief valve outlet (pipe must
be same size as outlet and the open end must not be threaded)
to an open drain, tub or sink, or other suitable drainage point
not subject to freezing. Failure to do so may cause water
damage or injury should relief valve release.

EXPANSION TANK

In a properly assembled system, the expanding water flows
into a expansion tank. This tank should be of the correct size.

The tank is filled with air. As the water expands it compresses
the air in the tank to form an air pressure cushion. This “spring-
like” cushion serves to maintain correct operating water
pressure regardless of water temperature. This assures a “full
measure” of a water, even in the highest radiation unit of the
system. It also prevents blowing off of the relief valve.

The air in the tank in the beginning (with system filled with cold
water) is sufficient for proper operation. The tank also serves
as a trap for excess air in the system. The air would cause
gurgling in the pipes and inefficient circulation in the radiators
if left in the system . It is possible for a tank to become
“waterlogged” (filled with water). It can also become overfilled
with air. This can happen after filling the system with new water.
Fittings provided on the tank and in the line to the tank are for
bleeding off excess water or air.

 When installing this tank, it is important:

1) That the tank be higher than the boiler top.

 2) That the pipe to the tank continuously rises up to the tank
(so that air can “bubble” up to it).

DIAPHRAGM TYPE EXPANSION TANK

The diaphragm type expansion tank (EX-TROL) takes the place
of the conventional expansion tank. Carefully read the
instructions packed with your EX-TROL tank assembly.

The EX-TROL tank comes to you with a 10-12 pounds per square
inch air charge. This is the same as the pressure produced in
the system by the automatic fill valve. When the system is first
filled, the EX TROL tank will contain little or no water.

As the water is heated its pressure increases. It expands into
the EX-TROL tank, compressing the air in the tank. This
compressed air cushion permits the water in the system to
expand as the temperature changes.

The diaphragm type tank can be mounted on the air purger
fitting or at any convenient place in the supply or return line.

AIR ELIMINATING FITTING (AIR PURGER)

An air purger is used to remove excess air from the system. It
is installed in the supply line. It will eliminate air from the water
before it reaches the radiators and bleed off this air.

MAIN AIR VENT FOR DOWN FLOW SYSTEMS
OR DIAPHRAGM TYPE EXPANSION TANK

Before a system is filled with water, there is air in the pipes and
radiation units. Some of it will be trapped as the system is filled .
It is possible to eliminate most of this air through the air vents
on the radiation units. A main air vent will speed and simplify
this. It should be installed on the highest point in the supply
main when all radiation is below top of boiler.

AUTOMATIC FILL VALVE

For safe, efficient operation, a hot water system must be

completely filled

 with water. Adding new water, when needed

can be done manually (by use of a hand valve in the water
supply line). This requires regular attention to the system’s
needs. An automatic fill valve accomplishes this without
attention. It is installed in the supply line on hot water boilers
only. The valve operates through water pressure differentials.
It does not require an electrical connection.

DRAIN VALVE

This manual valve Provides a means of draining all water from
the boiler and system. It is often installed in the 3/4” tapping at
the bottom of the end boiler section. Or it can be installed in a
tee where the return line enters the boi

l

er.

WATER TEMPERATURE CONTROL

The water temperature limit control in the relay is adjustable
and may be set as necessary. It may be set as low as 140°F,
or as high as 240°F. This depends on the type and amount of
radiation involved and weather conditions.

CIRCULATING PUMP

Every forced hot-water system requires a circulating pump. A
separate pump or zone valve is required for each zone, if you
have a two or more zone system. This pump must have the
capacity to provide the circulation required by your system.

VENT DAMPER

This product is an automatic, motorized stack damper that has
been developed to increase the efficiency of heating system
by reducing standby losses from the heating apparatus and
the conditioned air space. The damper closes the chimney
vent when the burner is off and fully opens it when combustion
is required.

Summary of Contents for PVWB

Page 1: ...t W Hot W Hot Wa a a a ater ter ter ter ter Boiler Boiler Boiler Boiler Boilers s s s s These Gas Fired Water Boilers are low pressure sectional cast iron boilers Designed Certified by C S A Canadian...

Page 2: ...WB 9D 9 280 226 197 7 30 BASIC BOILER UNIT NO DIMENSIONS Inches NATURAL AND PROPANE GAS GAS FIRED HOT WATER BOILERS MBH 1 000 Btuh British Thermal Unit Per Hour Boilers are equipped for altitudes up t...

Page 3: ...with the correct conversion information Check to be sure you have the right size boiler before starting the installation _ See rating and capacity table on previous page Also be sure the new boiler is...

Page 4: ...installed in the room Consult section 6 3 1 of the National Fuel Gas Code for further information including approved methods for reducing clearances in large rooms 5 Equipment shall be installed in a...

Page 5: ...hin 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure shall be provided The openings shall communicate directly or by the ducts with the outdoors or spaces crawl...

Page 6: ...at the pump A hot water boiler installed above radiation level must be equipped with a low water cutoff device A periodic inspection is necessary as is flushing of float type devices per manufacturer...

Page 7: ...s noted above 6 Slopepipeupfromboilertochimneynotlessthan1 4 perfoot Chimney and Vent Pipe Connection For boilers for connection to gas vents or chimneys vent installations shall be in accordance with...

Page 8: ...from a cigarette cigar or pipe 6 After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above return doorswindows ex...

Page 9: ...product carrying areas of the appliance must be checked annually by you with particular attention given to deterioration from corrosion or other sources If you see corrosion or other deterioration con...

Page 10: ...d suitable for LP gas on male threads only 3 Use ground joint unions 4 Install a sediment trap upstream of gas controls 5 Use two pipe wrenches when making the connection to the gas valve to keep it f...

Page 11: ...ffect on the operation of your boiler system BE SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT Locate the thermostat about five feet above the floor on an inside wall It may be mounted...

Page 12: ...S SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC WIRE OR ITS EQUIVALENT NOTE THE CIRCULATOR HARNESS IS FACTORY WIRED TO THE AQUASTAT THIS HARNESS NEEDS...

Page 13: ...THE ORIGINAL WIRE AS SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC WIRE OR ITS EQUIVALENT NOTE THE CIRCULATOR HARNESS IS FACTORY WIRED TO THE AQUASTAT...

Page 14: ...heated its pressure increases It expands into the EX TROL tank compressing the air in the tank This compressed air cushion permits the water in the system to expand as the temperature changes The diap...

Page 15: ...Boiler HOW A HOT WATER SYSTEM OPERATES Your entire heating system boiler piping and radiation units is filled with water As the water in the boiler is heated it is pumped from the top of the boiler t...

Page 16: ...fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system an...

Page 17: ...se to OFF Do not force Operating Your Boiler AUTOMATIC GAS VALVE The Automatic Gas Valve opens or closes according to the heat requirements of the thermostat and temperature limit control It closes if...

Page 18: ...gure 17 ADJUST LIMIT CONTROLS Instructions for each control are included with the controls These settings can be changed after you have had some idea how the system works Example If your system does n...

Page 19: ...ating conditions with the burners properly adjusted it should not be necessary to clean the boiler flue gas passages However to assure trouble free operation we recommend that you have the flue passag...

Page 20: ...power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It may be in closed posi...

Page 21: ...5 45 900 425 45 900 10 Knob Service Door Pair 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 137 02 513 11 Jacket Service Door 425 00 912 425 00 913 425 00 914 425 00 915...

Page 22: ...5 532 146 15 532 146 15 532 6A Main Burner with Pilot Bracket 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 146 15 531 Pilot Burner Nat 146 62 095 146 62 092 146 62 092...

Page 23: ...Taco 007 Circulator CI 001 03 10 1 x 2 Nipple 146 07 044 11 1 Bent Return Nipple 146 07 003 12 Intermittent Pilot Control 146 62 070 Spill Switch 36TX16 6281 340 F 146 60 002 Rollout Switch 146 29 002...

Page 24: ...14683002 Rev 3 November 2004...

Reviews: