- 44 -
Load/Unload Control
Manual Pulse Settings
Pulse Rate=
001sec
Pulse Width=
001sec
Technician Setpoints
Main Menu
Comp FLA Calibration
Sensor Calibration
Manual Control
Compressor Control
Sensors Override
Sensors Manual
Override
Supply Water Temp
Man Reading = 45.0°F [7.2°C]
Manual Override = NO
4.0 ELECTRICAL
NOTE: All compressors will revert back
to automatic control if the computer is
the computer is not given a load,
unload, or hold command at least once
every 15 minutes. A command can be
repeated to meet the 15 minute
requirement for manual control.
To the change the settings of
compressor load/Unload, follow the
above steps and go to compressor
control. Use down arrow key to move
the following and press to change the
settings.
4.3.5.7 Sensors
Override
Value of analog readings can be
temporary override during sensor
failure.
To override the analog readings, the
operator must be authorized at
technician level or higher.
Press technician key to go to technician
setpoints main menu and press enter
key five times to move the cursor to the
‘Sensors Override’ sub-menu:
The display is showing the data as
follows:
Use up or down arrow key to move the
cursor to the desired analog reading,
The display is showing the data as
follows:
Press enter key to move the cursor to
the “Man Reading” and use the up or
down arrow key to change the value of
the analog reading, press enter key
move the cursor to the “Manual
Override” to enable, or disable the
manual override control.
Repeat the above steps for other
sensors override.
Caution:
Sensors override require continuous
monitoring and observation by the field service
personnel at all time during the unit operation.
Faulty sensor shall be replaced as soon as
possible in order to allow the unit to be running in
automatic mode.
4.3.6 CONTROL
FUNCTIONS
4.3.6.1 Chilled Water Pump Interlock
And Flow Switch (CWP And
CWFS)
These are field installed switches, both
of which are used to ensure chilled
water flow before the unit is allowed to
start. Failure of either one during
operation will cause the compressor to
shut down.
A water flow alarm will be generated
and ‘Rest Alarm’ must be pressed to
clear the alarm.
4.3.6.2 Customer
Control
Interlock
Control contacts from an external
controller can be used to enable or
disable operation of the unit. The wiring
diagram specifies the terminals to
which the contacts must be wired. To
enable the unit, the contacts must be
closed. To disable the unit, the contacts
must be opened.
Summary of Contents for ACDS
Page 7: ...7 2 0 INSTALLATION FIGURE 2 3 2 ACDS RIGGING ACDS 010 ACDS 020...
Page 8: ...8 2 0 INSTALLATION ACDS 030 040 050 060 070 ACDS 080 090 100 120 ACDS 135 150 165 180...
Page 9: ...9 2 0 INSTALLATION FIGURE 2 4 2B DIMENSIONAL DATA ACDS 010...
Page 10: ...10 2 0 INSTALLATION ACDS 020...
Page 11: ...11 2 0 INSTALLATION ACDS 030...
Page 12: ...12 2 0 INSTALLATION ACDS 040...
Page 13: ...13 2 0 INSTALLATION ACDS 050 060 070...
Page 15: ...15 2 0 INSTALLATION ACDS 100 120...
Page 19: ...19 2 0 INSTALLATION ACDS 030 040 050 060 070 ACDS 080 090 100 120 135 150 ACDS 165 180...
Page 22: ...22 2 0 INSTALLATION FIGURE 2 7A FIGURE 2 7B FIGURE 2 7C FIGURE 2 7D FIGURE 2 7E...
Page 25: ...25 3 0 OPERATION FIGURE 3 2 1 TYPICAL PIPING SCHEMATIC ACDS 010 020 030...
Page 26: ...26 3 0 OPERATION ACDS 040 050 060 070...
Page 27: ...27 3 0 OPERATION ACDS 080 090 100 120...
Page 28: ...28 3 0 OPERATION ACDS 135 150...
Page 29: ...29 3 0 OPERATION ACDS 165 180...
Page 54: ...54 4 0 ELECTRICAL 4 9 TYPICAL WIRING SCHEMATIC ACDS 010...
Page 55: ...55 4 0 ELECTRICAL...
Page 56: ...56 4 0 ELECTRICAL ACDS 020...
Page 57: ...57 4 0 ELECTRICAL...
Page 58: ...58 4 0 ELECTRICAL ACDS 030...
Page 59: ...59 4 0 ELECTRICAL...
Page 60: ...60 4 0 ELECTRICAL ACDS 040...
Page 61: ...61 4 0 ELECTRICAL...
Page 62: ...62 4 0 ELECTRICAL ACDS 050 060 070...
Page 63: ...63 4 0 ELECTRICAL...
Page 64: ...64 4 0 ELECTRICAL ACDS 080 90...
Page 65: ...65 4 0 ELECTRICAL...
Page 66: ...66 4 0 ELECTRICAL...
Page 67: ...67 4 0 ELECTRICAL...
Page 68: ...68 4 0 ELECTRICAL ACDS 100...
Page 69: ...69 4 0 ELECTRICAL...
Page 70: ...70 4 0 ELECTRICAL...
Page 71: ...71 4 0 ELECTRICAL...
Page 72: ...72 4 0 ELECTRICAL ACDS 120...
Page 73: ...73 4 0 ELECTRICAL...
Page 74: ...74 4 0 ELECTRICAL...
Page 75: ...75 4 0 ELECTRICAL...
Page 76: ...76 4 0 ELECTRICAL ACDS 135...
Page 77: ...77 4 0 ELECTRICAL...
Page 78: ...78 4 0 ELECTRICAL...
Page 79: ...79 4 0 ELECTRICAL...
Page 80: ...80 4 0 ELECTRICAL ACDS 150...
Page 81: ...81 4 0 ELECTRICAL...
Page 82: ...82 4 0 ELECTRICAL...
Page 83: ...83 4 0 ELECTRICAL...
Page 84: ...84 4 0 ELECTRICAL ACDS 165 180...
Page 85: ...85 4 0 ELECTRICAL...
Page 86: ...86 4 0 ELECTRICAL...
Page 87: ...87 4 0 ELECTRICAL...