Service Manual
41
connected well, whether
there is welding off or
rosin joint on the electric
control board, if there is
any, it should be repaired.
3.When the 1 and 2 are both
normal, then the
components or integrated
circuit is damaged, the
electric control board
should be replaced.
E2
display
at off
state
flicker
2/4 SEC
display
at
on/off
state
room temp.
sensor fault
1.Check whether the
resistance of the sensor is
normal, when it is
abnormal the sensor
should be replaced.
2.Check whether there is short
circuit or open circuit in
the wire of the sensor, and
whether the plug is
connected well, whether
there is welding off or