Service Manual
40
at on
state
1/1 SEC
indication
state is removed, it will return
to normal condition
automatically
FF
display
at on
state
flicker
1/1 SEC
Outdoor Low
temperature
indication
Normal, the unit will stop
running when the outdoor
temperature is below
14DegF
display
at
on
state
flicker
1/3 SEC
anti cold wind
1.Normal (during heating
mode )
2.It will be removed when the
coil pipe temperature
sensor reaches certain
temperature.
E1
display
at off
state
display
at
on/off
state
Outdoor temp.
sensor fault
1.Check whether the
resistance of the sensor is
normal, when it is
abnormal the sensor
should be replaced.
2.Check whether there is short
circuit or open circuit in
the wire of the sensor, and
whether the plug is
Summary of Contents for DA-09