Service Manual
30
replace them.
The refrigerant leakage.
refill up refrigerant after
checking the
leak source
.
The set temperature is too high . reduce
the
set
temperature.
The condenser blocked by dust or
others.
clean the dust and dirt.
Too much quantity of refrigerant. take
the
redundant
refrigerant out.
Blockage in airinlet or air outlet. Clear the obstacles.
Air mixed in refrigerant.
refill the refrigerant after
vacuumizing
outdoor temperature is above 109
DegF
The indoor or outdoor fan motor is
running slow
Change this indoor or
outdoor fan motor
The compressor suction or
venting capability is very poor
Change the compressor or
outdoor unit
4-way valve slight mixes up
Change the 4-way valve
02 Cannot cool.
The fan doesn’t run (motor or
capacitor of fan failed, Poor
Check. Repair and replace.