4.3 Enable Supervision of Wireless Zones
NOTE (for PC5010 and PC5015 v1.x control panels only): In order for wireless
zones to be supervised, you must enable Double End of Line (DEOL) supervi-
sion in the control panel. For more information, refer to your Installation Manual.
NOTE (PC5010 v2.0 and higher, PC5015 v2.2 and higher, PC5008, PC1565,
PC585 only): For wireless supervision to work, you must enable the wireless
zone attribute on all wireless zones (sections [101] to [132], option [8] ON).
Wireless Supervisory Window
Each wireless zone (WLS904, WLS906, WLS906, or WLS907) will send a
supervisory signal every 12 minutes. If the receiver does not receive a signal
within the time programmed for the
Wireless Supervisory Window
, it will
generate a supervisory fault.
To program the wireless supervisory window:
1. Enter [
✱
][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132-RS Module Programming.
3. Enter sections [81].
4. Enter the time period for the supervisory window (valid entries are 01-24
hours).
5. To exit press [#].
WLS908 Panic Pendant
The panic pendant does not transmit a supervisory signal. This is so that the
user will be able to take it away from the premise. You must disable wireless
supervision for each zone a panic pendant is assigned to.
Disable/Enable Zone Supervision
All wireless zones have supervision enabled by default. To disable supervision
for any zone, enter the following at any system keypad:
1. Enter [
✱
][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132-RS Module Programming.
3. Enter sections [82], [83], [84] and [85]. Disable or enable supervision for
each wireless zone by turning each relevant option on or off.
4. To exit press [#].
O T H E R P R O G R A M M I N G