37
KEYPAD AND FIRE CIRCUIT HOOK-UP DIAGRAMS
KEYPAD HOOKUP
1 Each keypad has four coloured leads: red (RED), black (BLK), yellow (YEL), and green (GRN). Connect the leads to
the corresponding terminals on the panel.
2 Up to 3 keypads may be connected in parallel. DO NOT connect multiple keypads on the same loop.
3 The wiring table gives the maximum wire run for various gauges of wire. Wire run lenghts are calculated on the
maximum current drawn by the keypad (when all lights are ON).
4 For standby loading purposes, it is recommended that a current draw of 20 mA per keypad be used. This represents
the panel in a disarmed state with two zones in alarm.
NOTE:
If two wires of the same gauge are paralleled, the run length can be doubled. e.g.: If eight 22AWG wires (2 RED, 2
BLK, 2 YEL, 2 GRN) are run to the keypad, the run length would double from 540 feet (164.5 m) to 1080 feet (329 m).
PC3000RK Wiring Chart
Wire
Gauge
Maximum Run
Length Keypad to
Panel
24AWG
330' / 100m
22AWG
540' / 164m
20AWG
850' / 259m
19AWG
1000' /305m
18AWG
1360' /414m
FIRE CIRCUIT HOOKUP
Smoke Detector Power Loop Wiring Chart
Loop
Current
mA
AWG14
AWG16
AWG18
AWG19
AWG22
Maximum wire run to EOL relay in feet / meters
50
2750 / 838 1740 / 530 1090 / 332 869 / 264 433 / 131
100
1375 / 419 870 / 265 545 / 166 434 / 132
216 / 66
200
690 / 210 435 / 132
270 / 82
217 / 66
108 / 33
300
460 / 140
290 / 88
180 / 55
144 / 43
144 / 43
400
345 / 105
215 / 65
135 / 41
108 / 33
54 / 16
Bell Loop Wiring Chart
Bell
Current
mA
AWG14
AWG16
AWG18
AWG19
AWG22
Maximum wire run to EOL resistor in feet / meters
50
2750 / 838
1740 / 530 1090 / 332
869 / 264
433 / 131
100
1375 / 419
870 / 265
545 / 166
434 / 132
216 / 66
200
690 / 210
435 / 132
270 / 82
217 / 66
108 / 33
300
460 / 140
290 / 88
180 / 55
144 / 43
144 / 43
400
345 / 105
215 / 65
135 / 41
108 / 33
54 / 16
500
275 / 83
170 / 52
105 / 32
86 / 26
43 / 13
600
230 / 59
140 / 43
90 / 27
72 / 22
36 / 11
700
195 / 59
125 / 38
80 / 24
62 / 19
30 / 9
Alarm Initiating Loop
Wiring Chart
Wire
Gauge
Max. Run to
EOL Resistor
14AWG
15500' / 4724m
16AWG
9740' / 2968m
18AWG
6120' / 1865m
19AWG
4860' / 1481m
20AWG
3840' / 1170m
21AWG
3060' / 932m
22AWG
2420' / 737
Smoke detector must be latching type (BRK model 1812).
To reset smoke detectors, press and hold [
∗
][4].